10.5.1 Application examples
Chlorine regulation with feedforward control
CCA250
CA80
Flow, e.g. Promag53
A
BU
BK
BN
CCA250
INS
47
48
91
92
CA80
DIO
1
2
3
Dig.in
CA80: DIO
Dig.in: PFM
91
92
+
–
45
46
CA80
DIO
Dig.out: PFM
A0029239
62
Example of chlorine control with feedforward control
1
Connection of the inductive proximity switch INS of CCA250 to the digital input of the DIO module
2
Connection of the signal from a flowmeter to the digital input of the DIO module
3
Activation of a (pulse) dosing pump via the digital output of the DIO module
A
Dosing pump
Utilize the advantage of the effectively wear-free control with binary outputs versus a
control system with relay. With pulse frequency modulation (PFM), it is possible to achieve
virtually continuous dosing using a dosing pump with higher input frequency.
1. Connect the INS proximity switch of the CCA250 assembly to a digital input of the
DIO module (e.g. slot 6, port 1).
2. In the software, configure a controller and as the source select the binary input
(e.g.
Binary input 1
) to which the proximity switch is connected. (
Menu
/
Additional
functions
/
Controllers
/
Controller 1
/
Controller enable
=
Binary input 1
)
3.
Signal type
: For the selected input, select the factory setting (
Static signal
).
4. Connect the measured value of a flowmeter to the second input of the DIO module
(e.g. slot 6, port 2).
5.
Signal type
: for this input, select
PFM
. (
Menu
/
Inputs
/
Binary input
6:2
/
Signal
type
=
PFM
)
6.
Input variable
: select the corresponding measured value (
Flow rate
).
You can now use the input you have just configured as the disturbance variable
for your controller
1)
An activation code, Order No. 71211288, is necessary for the "feedforward control" function.
Содержание Liquiline CA80SI