Hauser
29
Note!
If the probe length is < 200 mm, no decimal point position is shown on the display.
Code
Reason
Alarm /
warning
Influence on
current input
Priority
A120
Please contact Hauser.
W
–
5
Check measuring system
E203
The capacitance measured is too low
A
22 mA
1
E777
Incorrect probe connected
A
22 mA
2
E204
The capacitance measured is too high
A
22 mA
3
A661
Electronics temperature is too high
W
4
A617
Δ
C too small during calibration
W
6
A620
The current is outside the permitted range
(3.8...20.5 mA).
There is no connection to measured value
W
3.8 mA
20.5 mA
7
Fault
Reason
Remedy
No
measured value
No supply voltage
Check power supply
Signal line faulty
Check signal line
Electronic insert faulty
- FEI20 directly connected to L1 and N
Only connect to transmitter power supply
unit
Incorrect
measured value
Incorrectly calibrated
Carry out full/empty calibration again
Insulation of probe rod damaged
Replace probe
Liquid conductivity too low
Select other measuring principle
Red LED flashing Alarm (A)/warning (W)
See Error Code table
en - Errorcode
en - Trouble-shooting
Factory reset!
Keep both keys (+ and –) pressed for
15 s - red LED flashing!
The full and empty calibration is reset
to the delivery status.
Содержание Liquicap T FMI21
Страница 4: ...4 Endress Hauser pl Post powanie z przyrz dem en Handling de Behandlung...
Страница 8: ...8 Endress Hauser pl Monta Od g ry en Installation From above de Einbau Von oben...
Страница 9: ...Endress Hauser 9 pl Nieprawid owy monta en Incorrect Installation de Falscher Einbau...
Страница 12: ...12 Endress Hauser pl Zamocowa uchwyty dystansowe en Provide spacer de Abstandhalter anbringen...
Страница 16: ...16 Endress Hauser pl Pod czenie elektryczne en Connection de Anschluss...
Страница 32: ...www pl endress com KA233F 00 a3 04 05 CCS FM6...