Liquicap M FTI51, FTI52
Commissioning
Hauser
57
6.2.2
Setting the measuring range
!
Note!
The choice of measuring range (0 to 500 pF and 0 to 1600 pF) depends on the function of the probe.
• If the probe is used as a limit switch, you can retain the factory setting of 0 to 500 pF.
• If the probe is used for two-point control, the following recommendations apply for vertical
installation:
– Measuring range from 0 to 500 pF for probe lengths up to 1 m
– Measuring range from 0 to 1600 pF for probe lengths up to 20 m
To set the range to 0 to 1600 pF, proceed as follows:
1.
Turn the function switch to position 4.
2.
Press the "–" key for at least 2 seconds until the green LED 2 lights up.
3.
Release the "–" key when the green LED 2 lights up.
Turn the function switch to position 2 to continue the calibration.
Function switch
position
Function
– key
+ key
Light emitting diodes (LED signals)
A
B
C
1 (green)
2 (green)
3 (red)
4 (green)
5 (green)
6 (yellow)
4
Measuring range
Press for <
On *
(500 pF)
Off
(1600 pF)
**
*
These settings are factory settings.
** Switch status signaling (on/off/flashing) depends on the mounting location selected and the failsafe mode (MIN/MAX) set.
The LED flashes if a calibration has not yet been carried out.
1
7
3
5
_
+
Содержание Liquicap M FTI51
Страница 90: ...Technical data Liquicap M FTI51 FTI52 90 Endress Hauser...
Страница 91: ...Liquicap M FTI51 FTI52 Technical data Endress Hauser 91...
Страница 94: ...Liquicap M FTI51 FTI52 Index 94 Endress Hauser...
Страница 96: ...www endress com worldwide BA299F 00 en 10 08 71082410 CCS FM SGML 6 0 71082410...