Levelflex FMP50 HART
Electrical connection
Hauser
23
2-wire; 4-20mA HART, 4-20mA
"Approval"
Terminal voltage U at
device
Maximum load R, depending on the supply voltage U
0
of the power
supply unit
All
Channel 1:
13.5 to 30 V
R [ ]
Ω
[V]
U0
10
13.5
24.5
20
30
0
500
A0034969
Channel 2:
12 to 30 V
R [ ]
W
V
U0 [ ]
10
12
23
20
30
0
500
A0022583
1)
Feature 020 of the product structure: option C
2)
Feature 010 in the product structure
3)
At ambient temperatures T
a
≤ -30 °C, a terminal voltage U ≥ 16 V is required to start the device with the
minimum failure current (3.6 mA).
4)
At ambient temperatures T
a
≤ -40 °C, the maximum terminal voltage must be limited to U ≤ 28 V.
5)
If the Bluetooth module is used, the minimum supply voltage increases by 2 V.
Integrated polarity reversal
protection
Yes
Permitted residual ripple
with f = 0 to 100 Hz
U
SS
< 1 V
Permitted residual ripple
with f = 100 to 10000 Hz
U
SS
< 10 mV