Levelflex FMP50 HART
Electrical connection
Hauser
21
6.1.3
Supply voltage
2-wire, 4-20mA HART, passive
2-wire; 4-20mA HART
"Approval"
Terminal voltage U at
device
Maximum load R, depending on the supply voltage U
0
of the power
supply unit
• Non-
hazardou
s
• Ex nA
• Ex ic
• CSA GP
11.5 to 35 V
U0 [V]
10
11.5
22.5
20
30
35
0
500
R [ ]
W
A0035511
Ex ia / IS
11.5 to 30 V
• Ex d / XP
• Ex ic[ia]
• Ex tD /
DIP
13.5 to 30 V
R [ ]
Ω
[V]
U0
10
13.5
24.5
20
30
0
500
A0034969
1)
Feature 020 of the product structure: option A
2)
Feature 010 in the product structure
3)
At ambient temperatures T
a
≤ -30 °C, a terminal voltage U ≥ 14 V is required to start the device with the
minimum failure current (3.6 mA). At ambient temperatures T
a
> 60 °C, a terminal voltage U ≥ 12 V is required to
start the device with the minimum failure current (3.6 mA). The start-up current can be configured. If the device
is operated with a fixed current I ≥ 4.5 mA (HART Multidrop mode), a voltage U ≥ 11.5 V suffices in the entire
ambient temperature range.
4)
If the Bluetooth module is used, the minimum supply voltage increases by 2 V.
5)
At ambient temperatures T
a
≤ -30 °C, a terminal voltage U ≥ 16 V is required to start the device with the
minimum failure current (3.6 mA).