Operation via FOUNDATION Fieldbus
TM
iTEMP TMT85
94
Hauser
2.
A0042931
Select one of these bits (here for example: Configurable Area Bit 1) and select the
Drift option from the corresponding selection list. Press Enter to confirm the option
selected.
3.
A0042932
Now go to the Resource Block and activate the corresponding bit (here: Configurable
Area Bit 1) in the FD_OFFSPEC_MAP parameter.
4. The measurement value status can now also be set for this event. With the
STATUS_SELECT_103 parameter, the measured value status BAD is selected for this
purpose via the selection menu.
14.7.4 Reasons for a diagnostic event and corrective action
In the FD_RECOMMEN_ACT parameter in the Resource Block, a description is displayed
for the diagnostic event with the highest priority that is currently active. This description
has the following structure:
Diagnostic number:Diagnostic text with channel (ch x):troubleshooting recommendations
separated by hyphens, e.g. for the diagnostic event sensor break: 41:Sensor break
ch01:Check electrical connection - Replace sensor - Check configuration of the connection
type
The value transmitted via the bus has the following structure: XXYYY
XX = Channel number
YYY = Diagnostic number
For the "Sensor break" example above, this value is 01041
14.8 Transmission of event messages over the bus
The process control system used must support the transmission of event messages.