iTEMP TMT71
Diagnostics and troubleshooting
Hauser
41
Diagnostic
number
Short text
Corrective measure
Status
signal
from the
factory
Customizable
Diagnosti
c
behavior
from the
factory
Customizable
Not
customizable
Not
customizable
043
Short-circuit
1. Check electrical connection.
2. Check sensor.
3. Replace sensor or cable.
F
Alarm
047
Sensor limit reached, sensor n
1. Check sensor.
2. Check process conditions.
S
Warning
145
Compensation reference point
1. Check terminal temperature.
2. Check external reference point.
F
Alarm
Diagnostics for the electronics
201
Electronics faulty
1. Restart device.
2. Replace electronics.
F
Alarm
221
Reference sensor defective
Replace device.
M
Alarm
Diagnostics for the configuration
401
Factory reset active
Factory reset active, please wait.
C
Warning
402
Initialization is active
Initialization active, please wait.
C
Warning
410
Data transfer failed
1. Check connection.
2. Retry data transfer.
F
Alarm
411
Upload/download active
Upload/download active, please wait.
C
Warning
435
Linearization incorrect
Check linearization.
F
Alarm
485
Simulation of the process
variable is active
Deactivate simulation.
C
Warning
491
Current output simulation
Deactivate simulation.
C
Warning
495
Diagnostic event simulation
active
Deactivate simulation.
C
Warning
531
Factory calibration missing
1. Contact service.
2. Replace device.
F
Alarm
537
Configuration
1. Check device configuration
2. Upload and download new configuration.
(In case of current output: check
configuration of analog output.)
F
Alarm
582
Sensor diagnostics TC
deactivated
Switch on diagnostics for thermocouple
measurement
C
Warning
Diagnostics for the process
801
Supply voltage too low
Increase supply voltage.
S
Alarm