Commissioning
Proline Promass 80
48
Hauser
6.4.2
Two current outputs: active/passive
The current outputs are configured as "active" or "passive" by means of various jumpers on the
current input submodule.
#
Warning!
Risk of electric shock. Exposed components carry dangerous voltages. Make sure that the power
supply is switched off before you remove the cover of the electronics compartment.
1.
Switch off power supply
2.
3.
Set the jumpers
"
Caution!
Risk of destroying the measuring device. Set the jumpers exactly as shown in the diagram.
Incorrectly set jumpers can cause overcurrents that would destroy either the measuring device or
external devices connected to it.
4.
Installation of the I/O board is the reverse of the removal procedure.
a0001214
Fig. 31:
Configuring current outputs with the aid of jumpers (I/O board)
1
Current output 1 with HART
1.1
Active current output (default)
1.2
Passive current output
2
Current output 2 (optional, plug-in module)
2.1
Active current output (default)
2.2
Passive current output
INPUT/OUTPUT
4
2
1
2.1
1.1
2.2
1.2
+
+
INPUT/OUTPUT
3
INPUT/OUTPUT
2