Micropilot FMR60B HART
Diagnostics and troubleshooting
Hauser
41
X
1
2
A0043759
1
Status signal
2
Status symbol with diagnostic event
Faults detected by the self-monitoring system of the device are displayed as a diagnostic
message in alternation with the measured value display.
3
2
1
X X X X
X X X
X
X
X X X X
X X X
X
X
S
i
S801
A0043103
1
Status signal
2
Status symbol with diagnostic event
3
Event text
Status signals
F
"Failure (F)" option
A device error has occurred. The measured value is no longer valid.
C
"Function check (C)" option
The device is in the service mode (e.g. during a simulation).
S
"Out of specification (S)" option
The device is being operated:
• Outside of its technical specifications (e.g. during startup or a cleaning)
• Outside of the configuration performed by the user (e.g. sensor frequency outside the
configured span)
M
"Maintenance required (M)" option
Maintenance required. The measured value remains valid.
Diagnostic event and event text
The fault can be identified by means of the diagnostic event. The event text helps you by
providing information about the fault. In addition, the corresponding status symbol is
displayed in front of the diagnostic event.