iTEMP TMT142B
Installation
Hauser
9
1
2
3
4
5
6
aaa
aaa
bbb
bbb
A0041675
1
Direct field transmitter mounting on sensor
1
Thermowell
2
Insert
3
Neck tube nipple and adapter
4
Sensor cables
5
Fieldbus cables
6
Fieldbus shielded cable
1. Mount the thermowell and screw down (1).
2. Screw the insert with the neck tube nipple and adapter into the transmitter (2). Seal the
nipple and adapter thread with silicone tape.
3. Guide the sensor cables (4) through the cable gland of the fieldbus transmitter housing
into the connection compartment.
4. Fit the field transmitter with the insert on the thermowell (1).
5. Mount the fieldbus shielded cable or fieldbus connector (6) on the opposite cable gland.
6. Guide the fieldbus cables (5) through the cable gland of the fieldbus transmitter housing
into the connection compartment.
7. Screw the cable gland tight as described in the
Ensuring the degree of protection
section.
The cable gland must meet explosion protection requirements. → 16
4.2.2
Remote mounting
NOTICE
Do not overtighten the mounting screws of the 2" pipe mounting bracket in order to
prevent any damage.
‣
Maximum torque = 6 Nm (4.43 lbf ft)