Electrical connection

iTEMP TMT142B

16

Hauser

5.5  

Ensuring the degree of protection

The measuring system meets all the requirements of IP67 protection. Compliance with the

following points is mandatory following installation in the field or servicing in order to ensure

that IP67 protection is maintained:

• The housing seals must be clean and undamaged when inserted into their grooves. The

seals must be dried, cleaned or replaced if necessary.

• The cables used for connection must be of the specified outside diameter (e.g. M20x1.5,

cable diameter 8 to 12 mm).

• Firmly tighten the cable gland. →   8,  16

• The cables must loop down before they enter the cable glands ("water trap"). This means

that any moisture that may form cannot enter the gland. Install the device in such a way

that the cable glands are not facing upwards. →   8,  16

• Replace unused cable glands with dummy plugs.

• Do not remove the grommet from the cable gland.

  A0024523

 8

Connection tips to retain IP67 protection

5.6  

Post-connection check

Device condition and specifications

Notes

Is the device or cable undamaged (visual check)?

--

Electrical connection

Notes

Does the supply voltage match the information on the
nameplate?

U = 11 to 36 V

DC

Do the cables have adequate strain relief?

Visual inspection

Are the power supply and signal cables connected
correctly?

→   11

Are all the screw terminals sufficiently tightened?

Are all cable entries mounted, tightened and leak-tight?

Housing cover installed and firmly tightened?

Содержание HART iTEMP TMT142B

Страница 1: ...g Instructions they are not a substitute for the Operating Instructions pertaining to the device For detailed information refer to the Operating Instructions and other documentation Available for all...

Страница 2: ...iTEMP TMT142B 2 Endress Hauser Order code Ext ord cd Ser no www endress com deviceviewer Endress Hauser Operations App XXXXXXXXXXXX XXXXX XXXXXX XXX XXXX XX Serial number 1 3 2 A0023555...

Страница 3: ...6 Post connection check 16 6 Operation options 17 6 1 Overview of operation options 17 6 2 Transmitter configuration 18 6 3 Access to the operating menu via the SmartBlue App 18 7 Commissioning 19 7 1...

Страница 4: ...avoid this situation can result in minor or medium injury NOTICE This symbol contains information on procedures and other facts which do not result in personal injury 1 3 Tool symbols Symbol Meaning A...

Страница 5: ...one sensor input for a resistance thermometer RTD thermocouples TC resistance and voltage transmitters The device is designed for installation in the field If the device is used in a manner not speci...

Страница 6: ...g information on the delivery note 4 Are the technical documentation and all other necessary documents provided If applicable are the Safety Instructions e g XA for hazardous areas provided If one of...

Страница 7: ...utput current consumption device revision firmware and hardware version degree of protection 1 4 Radio approval Bluetooth optional depending on the configuration 1 5 2 lines for the TAG name 1 6 Appro...

Страница 8: ...cates and approvals must be observed please see Ex certificates 4 1 2 Important ambient conditions Ambient temperature Without display 40 to 85 C 40 to 185 F With display 40 to 80 C 40 to 176 F With o...

Страница 9: ...and of the fieldbus transmitter housing into the connection compartment 4 Fit the field transmitter with the insert on the thermowell 1 5 Mount the fieldbus shielded cable or fieldbus connector 6 on t...

Страница 10: ...unting or with a 2 pipe mounting bracket 316L see the Accessories section Dimensions in mm in 4 3 Post installation check After installing the device carry out the following checks Device condition an...

Страница 11: ...ntact the supplier if you have any questions Do not occupy the display connection An incorrect connection can destroy the electronics NOTICE Do not overtighten the screw terminals as this could damage...

Страница 12: ...SD electrostatic discharge Protect the terminals from electrostatic discharge Failure to observe this may result in the destruction or malfunction of parts of the electronics Terminal assignment 3 3 3...

Страница 13: ...not have additional potential equalization mains frequency equalizing currents can occur that damage the cable or the shielding In such cases the shielding of the fieldbus cable is to be grounded on o...

Страница 14: ...shed by the HART FieldComm Group particularly HCF LIT 20 HART a technical summary TMT142B FieldCare DeviceCare HART Modem PLC 200 3 2 250 PMC731 PIC0001 Online 1 Group Select 2 PV 0 7 bar HELP SEND HO...

Страница 15: ...unding of the cable shield at one end 4 Optional grounding of the field device isolated from cable shielding 5 4 Special connection instructions If the device is fitted with a surge arrester module th...

Страница 16: ...they enter the cable glands water trap This means that any moisture that may form cannot enter the gland Install the device in such a way that the cable glands are not facing upwards 8 16 Replace unu...

Страница 17: ...essary remove the display with the fitting kit from the electronics module 4 Configure the Bluetooth function accordingly using the DIP switch In general the following applies switch to ON function en...

Страница 18: ...s technology Signal transmission via Bluetooth wireless technology uses a cryptographic technique tested by the Fraunhofer Institute The device is not visible via Bluetooth wireless technology without...

Страница 19: ...hrough the various items of information about the device swipe the screen to the side 7 Commissioning 7 1 Switching on the transmitter Once you have completed the post connection checks switch on the...

Страница 20: ...www addresses endress com 71486587 71486587...

Отзывы: