Commissioning
Gammapilot M FMG60 FOUNDATION Fieldbus
72
Hauser
option must be selected to stop the integration. The value is then automatically
transmitted to the
"Full calibration" (*16)
or
"Empty calibration" (*18)
function.
Avg. pulse rate
• The maximum integration time (= averaging time) is 1000 s. After this time, the
value is automatically transmitted to the
"Full calibration" (*16)
or
"Empty
calibration" (*18)
function.
• Integration is
not
terminated by pressing in the
"Avg. pulse rate" (*11)
function. Integration continues until
"Stop/edit"
is selected in the
"Calibration"
(*15)
function. For this reason, there may be a slight deviation between the last
average (integrated) pulse rate displayed and the final
"Full calibration" (*16)
or
"Empty calibration" (*18)
.
"Full calibration" (*16) / "Empty calibration" (*18)
Local display
Full calibration *16
33 cps
Local display
Empty calibration *18
2548 cps
The pulse rate of the full or empty calibration is displayed in this function. Press to
confirm the value. If a full or empty calibration has not yet been performed, "-1" is
displayed. There are two options if this occurs:
• Either return to the "Calibration" (*15) function and restart the calibration
• Or enter a known or calculated pulse rate (manual calibration)
"Next point" (*19)
Local display
Next point *19
✓
No
Yes
This function is used to specify whether an additional calibration point is to be entered or
not.
Options:
•
No
Select this option once both calibration points have been entered. The Gammapilot M
then returns to the group selection and the calibration is completed.
•
Yes
Select this option if only one calibration point has yet been entered. The Gammapilot M
then returns to the
"Calibration point" (*13)
function and the next point can be
entered.
7.4.4
Additional settings
After the basic setup, the Gammapilot M outputs the measured value via the Foundation
Fieldbus interface. Many additional functions are available for optimizing the measuring
point and can be configured as required. For a detailed description of all the device
functions, see BA00287F/00/EN, "Gammapilot M - Description of Device Functions", or the
CD-ROM supplied.