Commissioning
Micropilot FMR56, FMR57 FOUNDATION Fieldbus
38
Hauser
9.6
Configuring level measurement
100%
0%
R
BD
D
L
F
E
A0016934
19
Configuration parameters for level measurement in liquids
R
Reference point of measurement
D
Distance
L
Level
E
Empty calibration (= zero point)
F
Full calibration (= span)
1. Setup → Device tag
Enter a unique name for the measuring point to identify the device quickly within
the plant.
2. Setup → Distance unit
Used for the basic calibration (Empty / Full).
3. Setup → Bin type
Optimizes the signal filters for the respective bin type. Note: 'Workbench test'
deactivates all filters. This option should exclusively be used for tests.
Содержание FOUNDATION Fieldbus Micropilot FMR56
Страница 41: ......
Страница 42: ......
Страница 43: ......
Страница 44: ...www addresses endress com 71575727 71575727 ...