Commissioning
Micropilot FMR50 FOUNDATION Fieldbus
32
Hauser
6. Setup → Full calibration
Distance between minimum level (0%) and maximum level (100%).
7. Setup → Level
Currently measured level
8. Setup → Distance
Distance between lower edge of flange or thread and medium surface.
9. Setup → Signal quality
Displays the signal quality of the analyzed level echo.
10. Setup → Mapping → Confirm distance
Compare the distance displayed with the actual value to start recording an
interference echo map.
11. Setup → Advanced setup → Level → Level unit
Select the level unit: %, m, mm, ft, in (factory setting: %)
The reaction time of the device is preconfigured via the
Tank type
parameter. Advanced
configuration is possible in the
Advanced setup
submenu.
9.7
User-specific applications
To configure the parameters for user-specific applications, see:
BA01120F - Operating Instructions, FMR50, FOUNDATION Fieldbus
Also, for the
Expert
submenu:
GP01017F - Description of device parameters, FMR5x, FOUNDATION Fieldbus