EngyVolt RV15
Appendix
57
EngyVolt devices may be compatible with earlier releases of N2 software, but Johnson Controls only
supports integration issues on the above.
Support for Metasys integration
Please contact the nearest Jonson Controls Energy Efficency or Johnson Controls System & Services
representative. The address can be found on the Johnson Controls website.
Design considerations
When integrating the EngyVolt device equipment into a Metasys Network, keep the following
considerations in mind.
Make sure all EngyVolt device equipment is set up, started and running properly before attempting
to integrate with the Metasys Network.
A maximum of 32 devices can be connected to any one NCM N2 Bus segment, or up to 100 devices
if repeaters are used.
From the instrument set-up screen, the Coms option must be set to N2, then the address set to the
required value. All port settings will then be set automatically, see below.
Device address
1 to 255
Port set up:
Baud rate
9600
Duplex
Half
Word length
8
Stop bits
1
Parity
no
Interface
RS485
1)
The user has to make sure that the values given are set up in the EngyVolt device in order to ensure compatibility
with the N2 protocol network.
11.5.2 EngyVolt Metasys N2 point mapping table
Name
Description
Unit
ADF point
V1
Phase 1 line to neutral volts
V
1
V2
Phase 2 line to neutral volts
V
2
V3
Phase 3 line to neutral volts
V
3
A1
Phase 1 current
A
4
A2
Phase 2 current
A
5
A3
Phase 3 current
A
6
KP1
Phase 1 power
kW
7
KP2
Phase 2 power
kW
8
KP3
Phase 3 power
kW
9
KVA1
Phase 1 volt amps
kVA
10
KVA2
Phase 2 volt amps
kVA
11
KVA3
Phase 3 volt amps
kVA
12
KVAR1
Phase 1 volt amps reactive
kvar
13
KVAR2
Phase 2 volt amps reactive
kvar
14
* The values represented refer to the prefix "k" for energy values. For prefix "M" they are larger by factor 1000.