Commissioning
41
Submenu: Totalization (option)
Settings only required if this analog measuring point is to be totalized for calculating the
volume for example. For analysis periods, see "Signal analysis".
Totalization:
using the totalization function, the volume in m3 can be calculated from
an analog signal (e.g. flow in m
3
/h). Picklist:
no
, yes
Totalization Base:
select the corresponding time base. Example: ml/s -> time base
seconds (s)
; m
3
/h -> time base hours (h).
Total. Eng. Unit:
here, enter the unit for the volume determined by totalization (e.g.
"m
3
").
Scroll Display:
select the counter which should be displayed alternately with the
instantaneous value.
Factory setting: No, Only Instant Value
Low flow cut off:
specify how the device should perform low flow cut off:
Area Around Zero Point:
all values in the zero point range that are smaller than the
(absolute) "Low flow cut off" are not totalized (e.g. Low flow cut off = 0.1m/h: all values
<= -0.1m/h and >= 0.1m/h are totalized; all other values are discarded).
Absolute Value: all values that are smaller than the configured "Low flow cut off" are not
totalized (e.g. Low flow cut off = 0.1m/h: all values < 0.1 m/h are not totalized).
Low flow cut off:
specify the threshold value for the low flow cut off here.
Factory
setting: 0 %
Calc. Factor:
factor for calculating the totalized value (e.g. the transmitter returns l/s
-> totalization base = second -> desired unit is m
-> enter 0.001 as the factor).
Factory
setting: 1
Submenu: Fault Mode
Settings that lay down how this channel is to react under fault conditions (e.g. cable
open circuit, over range).
Fault Switches:
switches the selected relay under fault conditions. The terminal
numbers are shown in brackets. Picklist:
Not Used
, Relay x (Term. xx-xx)
Save Event:
stores an event in the event memory when a fault condition occurs.
Picklist:
No
, Yes
Cable Open Circ.:
The cable open circuit detection function can be switched on and
off here.
In the case of thermocouples: When thermocouples are switched in parallel, enabled
cable open circuit detection causes false alarms. Picklist:
no
, yes
In the 1 to 5 V range: Values < 0.8 V or > 5.2 V are assessed as cable open circuits.
There is no underrange/overrange. Picklist: no,
yes
NAMUR NE43:
Switch monitoring of the 4 to 20 mA range as per NAMUR
Recommendation NE43 on and off. The following error ranges apply when NE43 is
switched on:
3.8 mA: underrange (display shows: vvvvvv)
20.5 mA: overrange (display shows: ^^^^^^)
3.6 mA or
21.0 mA: open circuit (display shows: – – – –)
Picklist:
On
, Off
On Error
: Specify the value the unit should continue to use (for calculations) if the
measured value is not valid (e.g. cable open circuit).
Picklist: Last Valid Value, Range Start, Meas. Range End,
Value is Invalid
, Free
Configuration
Error Value:
only if "Free Configuration" is selected for the error.
The unit continues calculating with this value if a fault occurs.
Factory setting: 0 %
(See the following table)
Copy Settings
Copies settings from actual channel to selected channel. Picklist:
No
, in Analog Input x
"Signal Settings"
menu items
Configurable parameters
(factory settings are highlighted in bold)