Damping
τ
The damping influences the time with which the display in V0H0 and the output signal
react to a change in pressure.
#
Matrix Path through the
menus
Entry
Main group: Basic settings
1
Suppressing variations in measured values
V0H7
➤
Damping
τ
= 0…40 s
e.g. 20 s
Confirm
Selecting pressure units
After selecting new pressure units all pressure specific parameters on the pressure are
converted into the new units.
Example: After selecting the unit "psi" the measuring range from 0...10 bar is converted
into 0...145.5 psi.
#
Matrix Path through the
menus
Entry
Main group: Basic settings
1
Select pressure units
V0H9
➤
Selects
pressure units
e.g. mbar
Confirm
Units for operation mode "Pressure":
Selecting the flow rate
units
(Unit after Linearisation)
The unit for flow is selectable using "Unit after Linearisation" (V3H3) parameter. Selecting
a unit only helps to improve the display and does not affect the main measured value in
the matrix field V0H0.
Example: After selecting the unit "t/min", "112 kg/s" is displayed as "112 t/min".
#
Matrix Path through
menus
Entry
Main group: Basic settings
1
Select unit for flow rate units
V3H3
➤
Unit after
linearisation
e.g. kg/s
Confirm
Units for operation mode "Square Root" (flow):
I
0
τ
2
τ
3
τ
63 %
100 %
BA174Y25
output signal
jump
time
mbar
bar
Pa
hPa
kPa
MPa
mmH
2
O
mH
2
O
inH
2
O
ftH
2
O
psi
g/cm
2
kg/cm
2
kgf/cm
2
atm
lb/ft
2
Torr
mmHg
inHg
%
ft
3
/min
m
3
/h
l/s
ft
3
/s
m
3
/s
norm m
3
/h
std ft
3
/min
m
3
/min
USG/h
USG/d
MGal/d
g/min
kg/s
kg/min
kg/h
t/min
t/h
t/d
lb/s
lb/min
lb/h
7 Flow Measurement
Deltabar S
48