Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
Operation
Hauser
37
• The pressure applied must be within the nominal pressure limits of the sensor. See
information on the nameplate.
Perform position adjustment:
1. Pressure is present at device.
2. Press key for at least 3 seconds.
3. If the LED on the electronic insert lights up briefly, the pressure applied has been
accepted for position adjustment.
If the LED does not light up, the pressure applied was not accepted. Observe the input
limits. For error messages,
93, Section 9.2 "Diagnostic information on local
6.2.3
Function of the operating elements – onsite display connected
Key(s)
Meaning
O
– Navigate upwards in the picklist
– Edit numerical values or characters within a function
S
– Navigate downwards in the picklist
– Edit numerical values or characters within a function
F
– Confirm entry
– Go to next item
O
and
F
Contrast setting of onsite display: increase
S
and
F
Contrast setting of onsite display: reduce
O
and
S
ESC functions:
– Exit the editing mode without saving the altered value
– You are in the menu within a function group: the first time you press the keys
simultaneously, you go back one parameter in the function group. Every
subsequent time you press the keys simultaneously, you go up one level in the
menu.
– You are in the menu on a selection level: every time you press the keys
simultaneously, you go up one level in the menu.
Note:
For the terms function group, level, selection level,
P01-xxxxxxxx-19-xx-xx-xx-134
– DIP switch 1: for locking/unlocking parameters relevant to the measured value.
Factory setting: off (unlocked)
– DIP switch 2: for the simulation mode Factory setting: off (simulation mode off)
1
2
on
off
Sim.