Dynamic behavior
current output
Dead time, Time constant (T63)
P01-xxxxxxxx-05-xx-xx-xx-007
Presentation of the dead time and the time constant
Dynamic behavior HART
Dead time, Time constant (T63)
A typical parametrization for the PLC of 3 to 4 values per second results in the following total dead time:
Reading cycle
• HART commands: on average 3 to 4 per second on average.
The Deltabar S commands the BURST MODE function for cyclic value transmission via the HART
communication protocol.
Response time
250 ms
Cycle time (Update time)
On average 250...330 ms.
I
63 %
100 %
t
t
1
t
2
90 %
Type
Dead time t
1
Time constant (T63), t
2
PMD75
45 ms
• 10 mbar and 30 mbar measuring cell: 200 ms
• 100 mbar measuring cell: 60 ms
• 500 mbar measuring cell: 45 ms
• 3 bar measuring cell: 40 ms
• 16 bar and 40 bar measuring cell: 60 ms
FMD77, FMD78
dependent on the diaphragm seal
PMD70, FMD76
90 ms
• 25 mbar measuring cell: 4700 ms
• 100 mbar measuring cell: 280 ms
• 500 mbar measuring cell: 210 ms
• 3 bar measuring cell: 110 ms
Type
Dead time t
1
Time constant (T63), t
2
PMD75
295 ms
• 10 mbar and 30 mbar measuring cell: 200 ms
• 100 mbar measuring cell: 60 ms
• 500 mbar measuring cell: 45 ms
• 3 bar measuring cell: 40 ms
• 16 bar and 40 bar measuring cell: 60 ms
FMD77, FMD78
dependent on the diaphragm seal
PMD70, FMD76
340 ms
• 25 mbar measuring cell: 4700 ms
• 100 mbar measuring cell: 280 ms
• 500 mbar measuring cell: 210 ms
• 3 bar measuring cell: 110 ms