Deltabar FMD72
Description of device parameters
89
Set Min. Current (053)
Navigation
Setup
®
Advanced Setup
®
Current Output
®
Set Min. Current (053)
Write permission
Operators/Service engineers/Expert
Description
Enter lower current limit.
Some switching units accept no current smaller than 4.0 mA.
Options
• 3.8 mA
• 4.0 mA
Factory setting
3.8 mA
Output current (054)
Navigation
Setup
®
Advanced Setup
®
Current Output
®
Output Current (054)
Write permission
Operators/Service engineers/Expert
Description
Displays the current current value.
ALARM STATUS (071)
Navigation
Diagnosis
®
Diagnostic Code (071)
Write permission
No write permissions. Parameter is read only.
Description
Displays the diagnostic message with the highest priority currently present.
Last diag. code (072)
Navigation
Diagnosis
®
Last Diag. Code (072)
Write permission
No write permissions. Parameter is read only.
Description
Displays the last diagnostic message that occurred and was rectified.
Note
• Digital communication: the last message is displayed.
• Use the "Reset logbook" parameter to clear the messages listed in the parameter "Last diag. code".