Ceraphant PTC31B, PTP31B, PTP33B IO-Link
Technical data
Hauser
83
17.3 Performance characteristics of ceramic process
isolating diaphragm
17.3.1 Reference operating conditions
• As per IEC 60770
• Ambient temperature T
A
= constant, in the range of:+21 to +33 °C (+70 to +91 °F)
• Humidity φ = constant, in the range of 5 to 80 % rH
• Ambient pressure p
A
= constant, in the range of:860 to 1
060 mbar (12.47 to 15.37 psi)
• Position of measuring cell = constant, in range: horizontal ±1° (see also "Influence of the
installation position" section → 16)
• Zero based span
• Material of process isolating diaphragm: Al
2
O
3
(aluminum-oxide ceramic, Ceraphire
®
)
• Supply voltage: 24 V DC ±3 V DC
• Load: 320 Ω (at 4 to 20 mA output)
17.3.2 Measuring uncertainty for small absolute pressure measuring
ranges
The smallest extended uncertainty of measurement that can delivered by our
standards is:
• in range 1 to 30 mbar (0.0145 to 0.435 psi): 0.4 % of reading
• in range < 1 mbar (0.0145 psi): 1 % of reading.
17.3.3 Influence of the installation position
17.3.4 Resolution
Current output: min. 1.6 μA
Display: can be set (factory setting: presentation of the maximum accuracy of the
transmitter)
17.3.5 Reference accuracy
The reference accuracy contains the non-linearity [DIN EN 61298-2 3.11] including the
pressure hysteresis [DIN EN 61298-23.13] and non-repeatability [DIN EN 61298-2 3.11]
in accordance with the limit point method as per [DIN EN 60770].
Device
% of the calibrated span to the maximum turn down
Reference accuracy
Non-linearity
Non-repeatability
PTC31B - standard
±0.5
±0.1
±0.1
PTC31B - platinum
±0.3
±0.1
±0.1
1)
The non-linearity for the 40 bar (600 psi) sensor can be up to ± 0.15% of the calibrated span up to the
maximum turn down.