0
ATEX II3G
Proline Promag 50
24
Hauser
Connection of remote
version connecting cable
A0005616
Fig. 4:
Connection of remote version connecting cable
A
Wall-mounted housing remote version
B
Sensor connection housing, remote version, Promag W/P
C
Sensor connection housing, remote version, Promag H, DN
≤ 25
D
Sensor connection housing, remote version, Promag H, DN
≥
40
a
Ground terminals (are provided for connecting a potential equalization connection)
b
Connecting cable, coil current cable
c
Connecting cable, signal cable
n.c.
→
not connected, insulated cable screening
Wire colors
→
terminal number: 5/6 = brown, 7/8 = white, 4 = green, 37/38 = yellow
Terminal assignment / Connection data
"
Caution!
Only connecting cables supplied by Hauser must be used.
Terminal
6
5
7
8
4
37
36
42
41
S1
E1
E2
S2
GND
E
S
2
1
Designation
Measured variable
Pipe
EPD
Coil circuit
Electrode circuit
Functional values
U = 60 V
P = 2.5 W
a
6
5
5
7
7
8
4
4
37
37
36
42
42
41
41
E1 E2 GNDE
2
1
S1 E1 E2 S2GND E S
n.c.
n.c.
n.c.
n.c.
n.c.
n.c.
a
B
b
C
D
b
c
b
c
A
b
c
a
a
a