SET
SET
C.s.lo.
= Control set point lower limit.(for
selected output)
Adjustable between 0 and
C.s.Hi.
C.s.Hi.
= Control setpoint upper limit.(for
selected output)
Adjustable between
C.s.Lo.
and Upper scale
value.
a2.s.l
= Alarm
2
set value lower limit.
Adjustable between 0
and
A2.S.H
parameter value.
a2.s.H
= Alarm
2
set value upper limit.
Adjustable between
A2.S.L
parameter value and upper scale
value.
a2.Hy
=
Hysteresis of the Alarm2
output
.
Adjustable between 1 and 50 °C.
A2.st.
= The state of Alarm2 output.
Hi
=
If A2 output is above the set
value. (on)
lo
=
If A2 output is above the set
value.(off)
A2.Er.
=
State of Alarm2 output in the
case of sensor failure.
on
= A
2 output is probe failure (on).
off
= A
2
output is probe faiure (off).
A2.tp
= Function of Alarm
2
type.
Four kinds of functions can be
selected.
indE.
=
Independdnt
alarm
(Independent)
dE.
= Deviation
bAnd
= Band alarm (Band)
bAn.i
= Band with inhibition
inp.t.
=
Input type selection.
FE.cn.
= J type ,
nc.nA.
= K type
c.cn.
= T
type
p10.r.
=S type ,
P13.r.
= R type
thermocouple selection.
This parameter varies when changing
some parameters.
Unit
=
The temperature unit.
°
C
= °C,
°F
= °F
(This parameter varies when
changing some parameters.)
C.o.sE
=
Control output selection
C-A2
= C/A2 (Relay) output selection
SSR
= SSR output selection
F.kE.C.
=
Function key setting parameter
nonE
= Function key is off.
C2.S.A.
= The function key with 2.set value is used.
manu.
= Manual mode can be achieved with the
function key.
dSP.o
.
= Only the temperature display mode is
entered with function key.
C. Pb
=
Proportional band.(for selected
output)
Adjustable between
%0
.0
and
%100
.0.
C. Pb
= %0
.0,
On-Off
control is selected.
C. ti
=
Integral time.(for selected output)
Adjustable between 0 and 100.0 minutes.
C. ti
=
0.0,integral impact is disable.
parameter is different from “0”,this
parameter appears.
C. Pb
C.Hys
=
Hysteresis of the output.(for
selected output)
Adjustable between 1 and
50 °C.
= 0,this parameter is active.
C. Pb
C. td
=
Derivative time.(for selected output)
Asjustable between 0.00 and
25.00 minutes.
C. td
=
0.0, derivative time is disable.
parameter is different from”0”,this
parameter appears.
C. Pb
C. Ct.
=
Period time.(for selected output)
Adjustable between 1 and
250 second.
parameter is different is different
from“0”,this parameter appears.
C. Pb
C.p.st
=
The ratio of output power at the
setpoint.Adjustable between %0 and %100.
C.E.P.s
.
=
The percentage of faulty sensor
selected output power.Adjustable between
%0 and %100.
C.typ.
= Control output type
C.typ.
=
HEAt
means heatign control.
C.
typ
.
=
CooL
means cooling control.
While the parameter names appear,if and
keys are pressed together, returns to the program
mode.
S.Cod
=
Security menu access
code
.
It should be 2011.
Cosc.
=
Parameters of
CoN.o.
menu security access level code.
nonE
=
Invisible.
P.yEs
=
Modification can be done.
P. no
= Only visible.
m.SEt.
=
The percentage of manual output parameter.
Adjustable between %0 and %100.
This parameter allows manual adjustment of the output
power when the manual output selection.
C. Pb.
=
0
,
this parameter is not seen.
If
co.SE
parameter is different
from C-A2,this parameter is seen.
a.2.sc.
=
Parameters of
al2.o.
menu security access level code.
nonE
=
Invisible.
P.yEs
=
Modification can be done.
P. no
= Only visible.
Co.sc.
=
Parameters of
Conf.
menu security access level code.
nonE
=
Invisible.
P.yEs
=
Modification can be done.
P. no
= Only visible.
S.t.Sc.
=
Parameters of
S.tun.
men
u security access level code.
nonE
=
Invisible.
P.yEs
=
Modification can be done.
Co.sc.
=
Parameters of
Conf.
m
enu security access level code.
no
=
Parameter settings are not
change.
yEs
=
Parameter setting will be
restored.
2/
4
C.s.Lo.
C.s.Hi.
C. pb
C. ti
C. td
C.p.st
C.Hys
C. Ct.
C.typ
s.s.t.s.
C.E.p.s.
Con.o.
AL2.o.
ConF.
S.tun.
SEcu.
S.Cod.
Co.sc.
m.SEt.
a.2.sc.
Cn.sc.
S.t.sc.
dEF.P.
inp.t.
Unit
fltr.
C.o.sE
offs.
s.t.Co.
F.k.E.C.
A2.S.L
A2.S.H
A2.HY
A2.tP
A2.St.
A2.Er.
ET
2011
-
E
-0
4-R
SET
SET
SET
SET
SET
F
Programming mode
This parameter indicates the time to reach set point
value when the device is first enegised.
Adjustable between 0 and 250 minutes.
If 0 is selected, soft start feature will be enable and the
device reaches set point value quickly.
Setting
Pb = 0, so
ft
start feature will be disable.
Sst
.S
=Sofy starter timer set value
fLtr.
= Coefficient of digital filter.
Filter for display value.
Adjustable between 1 and
200
. If this parameter is 1,
digital filter runs most quick. If the parameter is
200
,
the filter run most slow. The value of parameter should
be increased in interference.
oFfS.
=
Offset value is added to the measurement value.
Adjusted between -100 and +100°C.The normal value is 0.
Offset value.
St.Cu
=
Self tune control
no
= Self tune is stopped.
yES
= Self tune is started.
Pressing key after the
yes
or no
selection, selt tune is started or
stopped.
Selt tune begins when the measurement,
PIdt.
message
and measurement value
are shown alternately.Self tune process
completed automatically after the
stco
parameter is done no and is entered to the
working mode. Self tune process begin when
the measured temperature is expected fall
below 90% of the set value the display shows
te.HI
message alternately.Expected to fall
below the temperature set point 60% evolved
and then self tune process starts automatically.
If asked to abort the self tune process,
St.Co
parameter is done
no
and key is
pressed.
SET
If key is pressed while holding key, the programming mode is enabled.
SET
F
Entering from the programming mode to the run mode:
If no key is pressed within 20 seconds during programming mode, the data is stored automatically and the run mode is entered.
Alternatively, the same function occurs first pressing key and key is pressing programming mode is entered.Then and keys are pressing
together,data is recorded and running mode is entered.
Modification Of Parameter Diagram
When holding key, the value of parameter flashes and using
keys the requested value can be adjusted.
If key is pressed and held 0.6 seconds, the value of the selected
parameter changes rapidly. If waited enough,the value increases 100 at each
step. After 1 second following the release of the key, initial condition is
returned.The same procedure is valid for the decrement key.
Chys
6 5 6
SET
SET
SET
SET
C.s.lO
.
inp.t.
A2.s.l
Co.sc.
C1.sE.
C.s.Hi
.
Unit
A2.s.H
A2.Sc.
C2.SE.
C. PB
Fltr.
A2Hy.
Cn.Sc.
A2.SE.
C.HyS
C.o.SE.
A2.tp
S.t.Sc.
C. ti
offs.
a2.st.
dEf.P.
C. td
f.k.E.C.
a2.Er.
a2.Er.
C. Ct
.
m.sEt.
C.P.St
.
C.EP.S
.
S.s.t.S
.
C.typ
.
TC input
TC input
TC input
TC input
TC input
Pt100 input
Pt100 input
Pt100 input
Pt100 input
Pt100 input
0
FE.cn.
0
0
25
2
2
C-A2
indE
P.yEs
P.yEs
400
P.yEs
400
P.yEs
500
4.0
0
Hi
no
1.00
nonE
on
no
20
50
0
0
0
HEat
-200
Pt.
-200
600
°
C
600
DEFAULT PARAMETERS
Set parameters
Control output
parameters
Alarm2 output
parameters
Configuration
parameters
Self tune
parameters
Security
parameters