EDT1323
PROGRAMMING DIAGRAM
FAN
LED
DEFROST
LED
Compressor
hysteresis
value
If this key is pressed,
COMPRESSOR setpoint
value appears.
Measurement
temperature
COMPRESSOR
setpoint value
SET
2/3
RUN MODE
°C
SET
EDT1323
ENDA
COMPRESSOR
LED
If this key is pressed,
hysteresis value for
compressor switch
appears.
If this key is pressed,
lower limit of the setpoint
appears.
If this key is pressed,
state of Fan control is
seen,
state of Fan
control
Lower limit of
the Setpoint
Rdý
2
-50
N
Rll
FaC
PROGRAMMING MODE
Means, thermostat probe is broken or failed or the cold room temperature is out of the
measurement range.
Means, measured value is out of the adjusted alarm limits.
Means, defrost probe is broken or failed or evaporator temperature is out of the measurement
scale range.
Er0
Er1
-30
ERROR MESSAGES
Used for increasing the setpoint value, as well as the
parameter when in programming. When held down for a few
seconds, the change rate accelerates.
When held down for 4 second in the run mode, manual defrost
starts.
Used for decreasing the setpoint value, as well as the parameter
when in programming. When held down for a few seconds, the
change rate accelerates.
Used for adjusting the value of the setpoint in
selected parameter in the programming mode.
the run mode and
for adjusting the
Increment
key
Decrement
key
Programming
key
SET
If both & keys are pressed and held for 5 seconds, programming mode is entered.
By using and keys while holding key, setpoint value
can be adjusted.
SET
By using and keys while holding key, compressor hysteresis
°C , Maximum = 20 °C
value can
be adjusted to a desired temperature.
Minimum = 1
By using and keys while holding key,
°C , Maximum = the value of the
ruL
parameter.
the lower limit of the setpoint can
be adjusted to a desired temperature.
Minimum = -50
By using and keys while holding key,
fan control can be selected as room
temperature dependent or not.
SET
SET
SET
The same procedure is also valid for adjusting the other parameters.
If any no key is pressed within 25 seconds, the device will time out back to the run mode. Alternatively, re-energising the device,
run mode is entered.
EDT1323
-E-04