– Page 7 –
iSaver DPFC 165 & 250 Series Manual
© 2021 Encorp Limited
Standard Specification for iSaver 240A
Model
iSAVER-240A-3Ph
Voltage Input
600 VAC 60Hz
Supply
Three Phase
Configuration
3 Phase – 4 Wire or 3 Wire
Current Rating
240A Nominal (247.5 kVAR)
Banks
1x27.5 + 1 x 55+ 2x82.5 kVAR
Minimum Correction
Bank activation at Reactive load >19.5 kVAR
Sequence
1:2:3:3:3
Electrical Steps
09
Logic
The unit is designed to operate in steps of 27.5 kVAR
Minimum Step
70% of the lowest Bank Capacity (19.5 kVAR)
Control Operation
Controlled real time switching output based on load requirements.
Controller
Micro controller based advanced electronic controller
Target Efficiency
> 98% (+/- 3%)
Energy Monitoring
HMI Module with IP controller board
Displayed Data (RMS)
V, I, kVA, kW, Hz, kWh, PF, kVAR, Hz, KVARh saved kVAh lag,THDv, THDi,
Deg. F
Display Meter
Zero Voltage/current, Over Voltage/current, Over Under compensation
Under Volt, Excess VTHD & ITHD, iSAVER UNB Current
Diagnostics
Phase & CT Sequence Indicator Short circuit and Over-load protection
(MCCB & MCB)
Bank Protection
Short circuit and Over-load protection (MCCB & MCB)
Construction
Robust standalone metal enclosure (indoor application only)
Dimensions
1600 (H) x 1100 (W) x 750 (D)
Weight
475Kg
Mounting
Floor Mounting with Foundation Bolts
Enclosure
Powder coated corrosion resistant sheet steel enclosure (RAL 7035)
Transient protection
Provided
Cable Entry
Bottom and Right-side entry provision.