![Encom Harmony Series Скачать руководство пользователя страница 16](http://html.mh-extra.com/html/encom/harmony-series/harmony-series_user-manual_2405992016.webp)
Harmony SBX Remote I/O Network Monitoring & Control User Manual
15
WIRELESS SETUP
In this configuration mode, you will be able to setup your radio to work on the radio network of your choice. The
following settings affect device connectivity on the network:
Ø
Network Address:
This lets you select an address number that is associated to a particular radio
network. By
default
, this is set to
0
. If you have more than one radio network,
it is recommended that a different address be used for each radio network.
The
network address needs to match in each radio within a particular network for
proper communication to work.
This option ranges from value 0 up to 254.
Example: one radio network uses Network Address 5 so all radios within that
network use Network Address 5, another radio network uses Network Address 8,
so all radios within that network use Network Address 8).
Ø
Unit Address:
This field will be greyed out as the system defaults the Master radio to a unit
address of 0.
This cannot be overridden
.
Ø
Hopping Pattern:
This lets you select a hop pattern value for the network. By
default
, this is set to
11
. It is recommended to select a value that is
different
from the hop pattern of
other
Encom equipment.
The primary hop pattern needs to match in each radio
in the particular network for proper communication to work.
Ø
Output Power:
Output Power is adjustable from a minimum of 1mW up to a maximum of 1W.
Ø
Mode:
This allows you to set the
SBX
to function as either a
Remote
radio or a
Repeater
.
Ø
Repeater Hopping Pattern:
The hopping pattern of your SBX in repeater mode. Note that this setting only
becomes available if you set the SBX mode to
Repeater
as shown below.