EN-KO Electronic Control Systems
AMF 4.0/ENG/K.K./02
16
generators. Panel doesn’t control this input for 2
minute after engine start. After 2 minute if input is
still active panel gives alarm, open generator
contactor, cools engine then stop generator.
If oil pressure sender that has both sender and switch is
used, switch terminal must be connected to this input and
this parameter is disabled.
P8
Auxiliary input 2 function
Functions are same as auxiliary input 1
If coolant temperature sender that has both sender and
switch is used, switch terminal must be connected to this
input and this parameter is disabled.
P9
Auxiliary input 3 function
Functions are same as auxiliary input 1
P10 Auxiliary input 4 function
Functions are same as auxiliary input 1
P11 Auxiliary input 1 activation
method
If this parameter is 0, input will be activated when it is
connected to battery negative. If this input is 1, input will be
activated, when input is disconnected from battery negative.
P12 Auxiliary input 2 activation
method
Same as auxiliary input 1
P13 Auxiliary input 3 activation
method
Same as auxiliary input 1
P14 Auxiliary input 4 activation
method
Same as auxiliary input 1
P15 Auxiliary output 1 function
This parameter select the functions of auxiliary output 1
•
Engine running:
If engine running signal generator
voltage, frequency or charge alternator warning lamb
voltage is detected this output will be activated.
•
Panel is in auto or test mode:
If panel is in
automatic or test mode this output is activated.
•
Yellow alarm:
If yellow alarm occurs, this output is
activated.
•
Red alarm:
If red alarm occurs, this output is
activated.
•
Common Alarm:
If yellow or red alarm occurs, this
output is activated.
•
Horn:
If horn is activated. This output will close and
open by intervals of 1 second.
•
Panel is in manual, auto or test mode:
If panel is in
manual, automatic or test mode, this output will be
activated.
•
Panel is in auto mode:
If panel is in automatic
mode, this output will be activated.
•
6 sec stop output during engine stop:
This output is
activated for 6 second during engine stopping
•
Fuel solenoid output:
This output can be used as
auxiliary fuel solenoid output
P16 Auxiliary output 2 function
Same as auxiliary output 1
P17 Auxiliary output 3 function
Same as auxiliary output 1
P18 Auxiliary output 1 activation If this parameter is selected as 0, when output is activated