UVX-Tin-side Detection System Operating Instructions
 

 

Document no. 10010604 

 

 

 

Programmable Parameters 

 
All  adjustments  made  to  these  parameters  are  stored  in  memory  and  are  retained  when  power  is 
removed.  To enter programming mode press and hold the 

P/-

 key for several seconds, the current 

threshold setting will be displayed.  Press and release the 

P/- 

key to scroll through the various settings.  

Press and release the 

T/+

 key to change a particular setting.  Press and hold the 

P/-

 for several seconds 

to return to the normal intensity display mode.  The user programmable items are described below. 

 

Threshold 

When the relative intensity level exceeds the threshold setting the red status LED will turn on and 
the discrete output will activate, indicating detection of the target.  When the relative intensity 
level  drops  below  the  threshold  (as  determined  by  the  hysteresis  setting),  the  red  LED  will 
extinguish, and the discrete output will de-activate.  The  threshold  setting allows the user to 
select the detection level. The default setting is 15. 
 
To  adjust  the  threshold,  enter  programming  mode,  press  and  hold  the 

P/-

  key  for  several 

seconds, the current threshold setting will be displayed.  Press and release the 

T/+ 

key to

 

increase 

the threshold level, to decrease the threshold level, continue to hold the

 T/+ 

key until the value 

approaches 99 then wraps around to 00.

  

 

 

 

LED Intensity Level (U) 

The LED intensity is indicated on the display as U1, U2 and U3 for low, medium and high intensity.  
Press and release the 

T/+ 

key to toggle through the 3 intensity levels.

  

The default setting is U2, 

medium intensity. 
 

Hysteresis Level (H) 

The hysteresis setting is indicated by H0 through H9.  The hysteresis level is how far below the 
threshold the signal must fall to de-activate or un-detect.  The hysteresis can be set from 0 to 9.  
For example, if the threshold is set at 25 and the intensity exceeds 25, the sensor will detect and 
activate its output.  With the hysteresis set to 5, the signal must drop to 20 to un-detect.  This 
feature  is  useful  in  cases  where  there  may  be  variation  within a  target  that  might  cause  the 
intensity  to  drop  below  the  threshold  slightly;  the  hysteresis  allows  the  output  to  remain 
activated until the level drops significantly.  Press and release the 

T/+ 

key to change the hysteresis 

setting.  The default setting is 2.   
 

Discrete Output Configuration 

This  setting  allows  the  user  to  select  either  normal  open  (no)  or  normally  closed  (nc) 
configuration.  The normally open configuration de-activates the output during normal un-detect 
operation, and activates the output upon detect.  The normally closed configuration activates the 
output during normal un-detect operation, and de-activates the output upon detect.  Press and 
release the 

T/+ 

key to toggle through the selections.  Default is normally open 

 

 

Содержание UVX-TIN-SIDE

Страница 1: ...O N S Operating Instructions 4564 Johnston Parkway Cleveland Ohio 44128 P 800 426 9912 F 216 518 9884 Sales Inquiries salessupport emxinc com Technical Support technical emxinc com www emxinc com UVX...

Страница 2: ...mized as described in this Instruction to achieve maximum life For this reason the LED is not covered by the manufacturer s warranty Connect an earth ground to the stud on the Optical Unit using minim...

Страница 3: ...ted at approximately 5 10mm from the surface of the glass A green LED indicates that the Optical Unit is powered The enclosure provides 4 mounting holes or 2 for the UVX tin side mini for user supplie...

Страница 4: ...ut Pulse 0 90 mS 10 steps Output Function NO NC selectable On Off Delay 150 uS Security LOCK UN LOCK keypad Power indicator Green LED Detect indicator Red LED Programming indicator Yellow LED Data ret...

Страница 5: ...ntensity Calibration Adjustment The calibration feature allows the displayed measurement to be adjusted to the desired value by the user Adjusting the measured value 1 Place target in sensor s field o...

Страница 6: ...T key until the value approaches 99 then wraps around to 00 LED Intensity Level U The LED intensity is indicated on the display as U1 U2 and U3 for low medium and high intensity Press and release the...

Страница 7: ...to identify the tin side of float glass by projecting the UV light source onto the target surface When the tin side is present the surface will emit light in the visible spectrum The receiver optics m...

Страница 8: ...to allow adjustments of sensor parameters 6 Connect the cable between the Optical Unit and the Control Unit 7 Connect the Control Unit wiring to the power source and PLC If necessary connect LED Enabl...

Страница 9: ...ors must not be connected in parallel Parallel connections may damage sensor output circuitry Analog Output The analog output is 0 5V with 20mV resolution 8 bit Any standard analog input channel typic...

Страница 10: ...d Mode while in Detect Display decimal points None illuminated LED low intensity One illuminated LED medium intensity Two illuminated LED high intensity M12 Connector Pin Assignments M12 Connector Wir...

Страница 11: ...ument no 10010604 Ordering Information UVX 300G C CU Control Unit OU TS2 Optical Unit M12 10 2 MF Cable 10P 5M M12 M F 240 240025 Power supply 24VDC regulated Accessories UVX300 BRKT UVX 300 C Bracket...

Страница 12: ...mal wear and tear abuse misuse overloading altered products damage caused by incorrect connections lightning damage or use other than intended design There is no warranty of merchantability There are...

Страница 13: ...ions 12 Document no 10010604 4564 Johnston Parkway Cleveland Ohio 44128 United States www emxinc com Technical Support 216 834 0761 E mail technical emxinc com Sales 216 518 9888 Fax 216 518 9884 E ma...

Отзывы: