©2015 EMS Security Group Ltd. All rights reserved.                                              TSD234 Iss 3 25/06/15 AJM 

 

Scroll down to “RE-ONLINE NODE” and press the “YES” key. 

 
Enter the Offline Nodes address number (between 2 and 30), then press the “YES” key. 

 
Once completed, check the slave panel’s status within the network and that it has been 

onlined  successfully  to  the  network.  Within  the  Radio  LAN  Menu  scroll  to  “Node  Table” 

and  press  the  “YES”  key.  This  will  display  each  networked  nodes’  status  and  will 
therefore,  highlight  whether  or  not  the  node  in  question  has  now  been  onlined  to  the 

network. The offline fault should clear from the panel. 
 

If unsuccessful, check the connections in P03265, between the panel and the LAN unit. 

 

NOTE  1:  the  same  process  can  be  carried  out  from  the  offline  slave  panel, 

without  the  requirement  of  a  node  address,  a  slave  panel  will  only 
communicate with the onsite master. 

 

NOTE 2: When onlining a node for the first time, you must go into Add/Delete 
Node on the master panel, and add the node, thus introducing the node into the 

node table. The node can now be re-onlined if it goes offline as above. 
 

 

8. Monitoring Nodes (Panels): 

 

Nodes can be checked for the amount of polls missed by checking the individual node’s 
missed poll counter.  

 
This will give an indication of the signalling between panels on the network. 

 

As a guideline, within a period of 8 hours, an acceptable number of missed polls would 
be  15.  However  many  more  could  mean  there  are  communication  problems  and  the 

problem node should be investigated. 
 

NOTE: missed poll lists are automatically reset at midnight. 

 

This  can  be  found  by  entering  the  Node Table  option  within  the  Radio  LAN  menu. This 

also  states  each  nodes  status  (ONLINE,  OFFLINE,  MISSING  or  SEARCHING),  where 
missing identifies an unused slot and searching is where the master panel is looking for a 

slave  panel.  Nodes  offline  are  caused  by  slave  nodes  failing  to  communicate  with  the 
master node. Any offline nodes can now be re-onlined by following the “Should the Radio 

LAN go offline” section. 

 
To  clear  the  missed  polls  list  by  accessing  the  “Radio  LAN”  menu.  Scroll  down  to 

advanced. Press the “YES” key. Scroll down to “Clear Missed Polls” and press the “YES” 
key.  Viewing  of  further  node  information  is  accessible  within  the  “Node  table  in  the 

“Advanced”  menu,  listed  above  the  “Clear  Missed  Polls”  option.  By  entering  the  “Node 

table”, each node can be viewed for their ONLINE/OFFLINE status and their number of 
missed polls.  

 

 
 
 
 

Содержание FirePoint System 5000

Страница 1: ...5000 RADIO LAN COMMUNICATION GUIDE...

Страница 2: ...RICAL INSTALLATION 4 5 FACTORY SUPPLIED PRE PROGRAMMED SYSTEMS 6 5 FACTORY SUPPLIED PRE PROGRAMMED SYSTEMS 7 6 SHOULD A LAN UNIT GO OFFLINE ON THE 485 BUS 7 7 SHOULD THE RADIO LAN GO OFFLINE 8 8 MONIT...

Страница 3: ...ls together The Radio LAN Module is hardwired to it s allocated control panel via a 2 core screened fireproof cable This then enables communication between control panels via radio therefore the need...

Страница 4: ...screws situated on the front lid The front section of the unit can now be removed Check that the front tamper switch operates when the lid is removed Should the microswitch not operate carefully adjus...

Страница 5: ...EMS 5000 FIREPOINT 2015 EMS Security Group Ltd All rights reserved TSD234 Iss 3 25 06 15 AJM 5...

Страница 6: ...Finish TIME Network Router Setup local NUA View Network NUA Network Name Control Routing Send Test Rem Rxer DISABLED Push YES to change Push NO to escape Push YES NO TIME Collector ENABLED Push YES to...

Страница 7: ...he master panel will automatically try to re online the pre programmed slave panels This can take up to 5 minutes to complete With control panels offline an OL fault will be displayed at the master pa...

Страница 8: ...bove The offline fault should clear from the panel 7 Should the Radio LAN go offline The following type of fault screen should be displayed Should such a fault be listed as previously shown the node p...

Страница 9: ...odes Panels Nodes can be checked for the amount of polls missed by checking the individual node s missed poll counter This will give an indication of the signalling between panels on the network As a...

Страница 10: ...e number The third row details values of information that is currently being sent The fourth line gives information of the nodes current status Eg Online or Offline With reference to the second line b...

Страница 11: ...peater panels are allowed on each system To change panel s to have this functionality at the main panel Access the Main menu Scroll down to Fire DB and press the YES key Now scroll down the menu until...

Страница 12: ...21100 then press the YES key and the screen will now display 6 Press the button until the screen displays 7 Press the YES key followed 0 key on the Keypad the screen will now display 8 Press the butto...

Страница 13: ...ll now display 19 Press the button until the screen displays 20 Press the YES key The screen will now display Re online Device Bus Master Setup Bus Remote Setup Yes Select Time Master Setup Polling Ba...

Страница 14: ...y 30 The Rem Rxer should be set to DISABLED press the YES key to change Otherwise press the NO key The screen will display Reply Baudrate Port to use Yes Select Time Remote Port 0 0 Off 1 RS485 2 PAGE...

Страница 15: ...utton until the screen displays 40 Press the YES key and the screen will display 41 The Routing should be set to ENABLED If already set press the NO key If DISABLED press the YES Key followed by the N...

Страница 16: ...ote The Site ID is factory set and can only be altered by entering an EMS engineering password Note This must match on all control panels on the radio board network for communication to take place 48...

Страница 17: ...al timer value varies depending on the number of slave panels within the system The time can be calculated using the table below Number of Slaves including Mimics Applicable Poll Interval Timer Values...

Страница 18: ...EMS 5000 FIREPOINT 2015 EMS Security Group Ltd All rights reserved TSD234 Iss 3 25 06 15 AJM 18...

Страница 19: ...S key followed by entering 3600 Now press the YES key and the screen should display 58 Now press the NO key until the screen displays 59 Turn the control keyswitch to the off position and the screen w...

Страница 20: ...cies UHF 458 5 459 5 MHz Transceiver Operating Temperature 10 to 55 degrees C Humidity Up to 75 non condensing Channel Spacing 25 kHz Output Transmitter Power 0 75W 500 mW 27DBH Supply 230v ac Current...

Страница 21: ...EMS 5000 FIREPOINT 2015 EMS Security Group Ltd All rights reserved TSD234 Iss 3 25 06 15 AJM 21...

Страница 22: ...EMS 5000 FIREPOINT 2015 EMS Security Group Ltd All rights reserved TSD234 Iss 3 25 06 15 AJM 22...

Отзывы: