After making sure all the connections are correct, the unit can be switched on. (It is 
recommended that any switching of the motor be carried out by switching the supply to the 
EnviroStart and not by switching the load). As power is applied the green Power-on LED 
should light up on the front of the unit, the motor should start turning immediately, ramping 
from stationary to full speed. It will take approximately 2.5s after the motor has reached its 
top of ramp speed before the energy saving routine is initiated. Depending upon the 
operational mode selected, fully automatic or fixed pedestal voltage, (see below), the 
optimization routine will then take approximately fifteen seconds to fully establish itself at 
which point the amber Energy Save LED will come on. (During this time it is likely that the 
Red Fault LED may flicker, this indicates only that the unit is establishing the parameters for 
an acceptable energy saving level for the motor). Depending upon mode and the level of 
savings being achieved the amber Energy Save LED may be on constantly or flicker on and 
off; either condition is perfectly normal. 

During the course of normal operation, the red Fault LED may flicker on and off occasionally 
as the optimization process establishes the torque limits for the motor and load combination; 
this is perfectly normal. 

 

4.3 COMMISSIONING 

It is necessary to establish the “safe operating level” mode for the EnviroStart with the given 
motor-load combination. In the first instance, unless otherwise directed, always try the 
default setting for the unit; this is Automatic Mode – Level 2, as indicated within the Table 2 
below. If the motor runs up, EnviroStart goes into saving mode, (as indicated by the amber 
Run LED flickering on and off) and the motor remains stable throughout any load variations, 
(including re-starts if the unit is externally controlled by say a thermostat or PLC), then you 
may want to try Automatic Mode – Level 1.  This level will provide a slightly higher degree of 
saving if the motor-load combination can handle the voltage and current reductions created 
by the EnviroStart.  If the motor becomes unstable and is unable to maintain the load torque 
requirement then try Automatic Mode – Level 3, and so on to Level 4. If the Automatic Mode 
levels do not provide a capability to maintain the motor load demands then move to the 
Pedestal Voltage Modes, shown in Table 3. This Mode provides four operating levels. If 
Automatic Mode – Level 4 has not worked then move to Pedestal Voltage Mode Level 1 and 
work through to Level 4.  If none of the Automatic Modes works then one of the Pedestal 
Voltage Modes, will. 

 

4.3.1 ESTABLISHING ENERGY SAVINGS 

Establishing the current and voltage levels without energy savings can be achieved by 
setting DIP Switch 1 into the ON position thereby disabling energy savings. The motor will 
be supplied with full current and full voltage as though the EnviroStart was not in circuit. 
Measuring the current and voltage in this condition and then referencing that against the 
current and voltage with SIP Switch 1 in the OFF position will allow you to determine the 
savings levels being achieved by the EnviroStart. In this always be careful to establish the 
power levels over a period of time rather than spot checks, as these can be unreliable 
indicators or true power. 

 

4.3.2 FAULT CONDITIONS 

If the motor sounds as though it is running unevenly or appears to stall at any time during its 
operation then please see the instructions below, on backstop settings. 

If the fault light comes on for more than a short period, switch off the unit for five minutes to 
allow the EnviroStart to cool and then switch on again. If the fault lamp comes back on 

Содержание 110-SPMECG6-10A

Страница 1: ...Single Phase Motor Energy Control Page 1 of 20 EnviroStart Single Phase Motor Energy Control Installation Commissioning Guide Version 2 1 January 2009 4A through 25A...

Страница 2: ...t 5 When the EnviroStart is connected to the mains the output connections U V and W should be treated as being live even if the load is not being driven 6 The control I O terminals are isolated from m...

Страница 3: ...8 LIGHTNING STRIKE 8 3 9 CONTROL VOLTAGE TRANSIENTS 8 3 10 INTERFACE CONNECTIONS 9 3 11 EMISSIONS 9 3 12 CABLE AND FUSE RATINGS 9 4 GENERAL INSTALLATION CONSIDERATIONS 10 4 1 GENERAL PROCEDURES 10 4 1...

Страница 4: ...even and a half years In the unlikely event that you do need further support please contact your local EMS European Distributor or failing that contact us directly either by e mail or fax All details...

Страница 5: ...ture relative humidity do affect sizing and failing to take proper notice of such conditions will invalidate any warranty associated with the system as supplied Where the EnviroStart is expected to op...

Страница 6: ...directives plus IEC and local industrial standards Units must be installed by a suitably qualified person to comply with general good electrical engineering practices and regulations with strict refe...

Страница 7: ...ING HUMIDITY Up to 95 Non Condensing Conformally Coated Systems Can Be Provided OPERATING TEMP 15o C to 40o C De rate current by 20 10o C ALTITUDE 4000m Above Sea Level De rate Current by 1 100m Above...

Страница 8: ...TS Ltd of Bromsgrove Worcestershire 18th July 2003 3 4 HEAT LOSSES For heat calculation purposes it should be assumed that EnviroStart units have a power loss of 4W A at full conduction 3 5 CONTROL PA...

Страница 9: ...in the table below It is recommended that all cable be tri rated compliant with BS 6231 and that all fuses be motor rated bolt fitting compliant with BS 88 Part 2 It is not necessary to use motor rat...

Страница 10: ...circuit board Make sure the earth cables are connected between the box lid and circuit board terminal block and replace the lid If the EnviroStart has been pre wired then the cable supplied may be eit...

Страница 11: ...tor N Base Plate Connector Motor Feed Neutral Earth Base Plate Connector Earth 4 2 SETTING UP All EnviroStart DIP Switches are polled continuously and it should be possible to make changes whilst the...

Страница 12: ...ckering on and off and the motor remains stable throughout any load variations including re starts if the unit is externally controlled by say a thermostat or PLC then you may want to try Automatic Mo...

Страница 13: ...following settings can be made The settings correspond to limiting how far the voltage applied to the motor will drop The lower the drop in voltage the more power savings will be achieved The reason...

Страница 14: ...he voltages shown in Table 3 are not absolute but indications only Input voltage and load conditions will cause the output voltage to change from that shown based on a supply voltage of 220V 4 3 4 SOF...

Страница 15: ...RS LED 1 Energy Save Enabled On to indicate that unit is running in energy save mode and is within a pre set band of energy savings around the level as is set by DIP Switches 2 3 and 4 LED 2 Power On...

Страница 16: ...Single Phase Motor Energy Control Page 16 of 20...

Страница 17: ...Single Phase Motor Energy Control Page 17 of 20 5 2 GENERALISED INSTALLATION DIAGRAM INSTALLATION AND COMMISSIONING GUIDE END...

Страница 18: ...NDIX 1 CONNECTION AND WIRING DIAGRAM 4A AND 10A Cable Connection Main Supply with Auxiliary 240V Connection DIP Switch Setting MEC Mode and Saving Levels Indicators showing Power On Run and Fault Cond...

Страница 19: ...Single Phase Motor Energy Control Page 19 of 20 CONNECTION AND WIRING DIAGRAM 25A NO PICTURE IS AVAILABLE AT THIS TIME...

Страница 20: ...Single Phase Motor Energy Control Page 20 of 20 APPENDIX 2 Mechanical Drawings 25A 4A and 10A...

Отзывы: