background image

16010-10-0314

Page 6

Water vapor is a by-product of gas combustion. An unvented room 

heater produces approximately one (1) ounce (30ml) of water for 

every 1,000 BTU's (.3KW's) of gas input per hour. 
Unvented room heaters must be used as supplemental heat (a 

room) rather than a primary heat source (an entire house). In most 

supplemental heat applications, the water vapor does not create a 

problem. In most applications, the water vapor enhances the low 

humidity atmosphere experienced during cold weather. 

The following steps will help insure that water vapor does not 

become a problem.  

1.  Be sure the heater is sized properly for the application, including 

ample combustion air and circulation air.

2.  If high humidity is experienced, a dehumidifier may be used to 

help lower the water vapor content of the air.

3.  Do not use an unvented room heater as the primary heat source 

(an entire house).

Provisions for Adequate Combustion and Ventilation Air

This heater shall not be installed in a confined space or unusually 

tight construction unless provisions are provided for adequate 

combustion and ventilation air.

A confined space is an area with volume less than 50 cubic feet per 

1,000 Btuh of the combined input rates of all appliances drawing 

combustion air from that space. Small areas such as equipment 

rooms are confined spaces. Furnaces installed in a confined space 

which supply heated air to areas outside the space must draw return 

air from outside the space through tightly sealed return air ducts. A 

confined space must have 2 openings into the space fro combustion 

air. One opening must be within 12 inches of the ceiling and the 

other must be within 12 inches of the floor. The required sizing of 

these openings is determined by whether inside or outside air is 

used to support combustion, the method by which the air is brought 

to the space (vertical or horizontal duct) and by the total input rate 

of all appliances in the space.
The following example is for determining the volume of a typical 

area in which the  SR-18BC may be located and for determining if 

this area fits the definition of an unconfined space.

The maximum input of the  SR-18BC is 18,000 Btu per hour.  Based 

on the 50 cubic feet per 1,000 Btu per hour formula, the 

minimum

 

area that is an unconfined space for installation of the  SR-18BC 

is 900 cubic feet, 50 cubic feet x 18 = 900 cubic feet. To determine 

the cubic feet of the area in which the  SR-18BC is to be installed, 

measure the length, width and height of the area.  Example:  The 

area measures 13 feet in length, 9 feet in width and 8 feet in height, 

the area is 936 cubic feet.  The  SR-18BC can be installed in this 

unconfined space with no requirement to provide additional com

-

bustion and ventilation air.

 

WARNING

If the area in which the heater may be operated is smaller than that 

defined as an unconfined space or if the building is of unusually 

tight construction, provide adequate combustion and ventilation 

air by one of the methods described in the National Fuel Gas 

Code, ANSI Z223.1/NFPA54, Air for Combustion and Ventilation, 

or applicable local codes.

Unusually Tight Construction

The air that leaks around doors and windows may provide enough 

fresh air for combustion and ventilation. However, in buildings of 

unusually tight construction, you must provide additional fresh air.

  Unusually  tight  construction  is  defined  as  construction 

where:

a.  Walls and ceilings exposed to the outside atmosphere have 

a continuous water vapor retarder with a rating of one perm 

or less with openings gasketed or sealed, and

b.  Weatherstripping has been added on openable windows and 

doors, and

c.  Caulking or sealants are applied to areas such as joints 

around window and door frames, between sole plates and 

floors, between wall-ceiling joints, between wall panels, at 

penetrations for plumbing, electrical, and gas lines, and at 

other openings. 

If the heater is installed in a building of unusually tight construction, 

adequate air for combustion, ventilation and dilution of flue gases 

shall be provided in accordance with ANSI Z223.1/NFPA54.

PROVISIONS FOR ADEQUATE COMBUSTION & VENTILATION AIR

WATER VAPOR: A BY-PRODUCT OF UNVENTED ROOM HEATERS

Содержание SR-10BC-3

Страница 1: ...ace Unvented room heaters are NOT FOR COMMERCIAL OR INDUSTRIAL USE WATER VAPOR A BY PRODUCT OF UNVENTED ROOM HEATERS Water vapor is a by product of gas combustion An unventedroomheaterproducesapproximatelyone 1 ounce 30ml of water for every 1 000 BTU s 3KW s of gas input per hour Refer to page 6 Installer Leave this manual with the appliance Consumer Retain this manual for future reference Do not ...

Страница 2: ... Mount Installation 10 11 Optional Floor Stand Installation 12 Lighting Instructions 13 Main Burner Flame Characteristics 14 Pilot Flame Characteristics 15 Main Burner Operation 15 Appliance Maintenance 16 Troubleshooting 16 SR 6 and SR 10 Parts List 17 SR 18 Parts List 18 How To Order Repair Parts 18 SR 6 Parts View 19 SR 10 Parts View 20 SR 18 Parts View 21 Master Parts Distributor List 22 How T...

Страница 3: ...ust be replaced prior to operating the heater Keep appliance area clear and free from combustible materials gasoline and other flammable vapors and liquids WARNING Failure to keep the primary air opening s of the burner s clean may result in sooting and property damage WARNING When used without adequate combustion and ventilation air heater may give off CARBON MONOXIDE an odorless poisonous gas Do...

Страница 4: ...erform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption on walls of newcylindersandtanks ispossible Therefore peopleshould be particularly alert and careful when new tanks or cylinders are placed in service Odor fade can occur in new tanks or reinstalled old tank...

Страница 5: ...alling Agency Installation and replacement of gas piping gas utilization equipment or accessories and repair and servicing of equipment shall be performed only by a qualified agency The term qualified agency means any individual firm corporation or company that either in person or through a representative is engaged in and is responsible for a the installation testing or replacement of gas piping ...

Страница 6: ... volume of a typical area in which the SR 18BC may be located and for determining if this area fits the definition of an unconfined space The maximum input of the SR 18BC is 18 000 Btu per hour Based on the 50 cubic feet per 1 000 Btu per hour formula the minimum area that is an unconfined space for installation of the SR 18BC is 900 cubic feet 50 cubic feet x 18 900 cubic feet To determine the cu...

Страница 7: ... following gas connectors is recommended ANS Z21 24Appliance Connectors of Corrugated MetalTubing and Fittings ANSZ21 45AssembledFlexibleApplianceConnectorsofOther Than All Metal Construction The above connectors may be used if acceptable by the authority having jurisdiction Pressure Testing of the Gas Supply System 1 To check the inlet pressure to the gas valve a 1 8 3mm N P T plugged tapping acc...

Страница 8: ... WINDOW SILL OR SHELF 12 MAX 305mm 24 MIN 610mm 0 0mm CLEARANCE TO REAR WALL 10 MIN 254mm SIDE VIEW 2 MIN 51mm FLOOR CEILING SIDE WALL WINDOW SILL OR SHELF 24 MIN 610mm 6 MIN 152 mm 6 MIN 152mm 10 MIN 254mm 2 MIN 51 mm FLOOR When facing the front of the appliance the following minimum clearances to combustible construction must be maintained Left side 6 inches 152mm Right side 6 inches 152mm Do no...

Страница 9: ...on must be maintained Left side 6 inches 152mm Right side 6 inches 152mm Do not install in alcove or closet Rear wall 0 inches 0mm Ceiling 36 inches 914mm Minimum vertical clearance from a projection above the appliance shelves window sills etc 36 inches 914mm Floor top surface of carpeting tile etc 2 inches 51mm Provide adequate clearances around air openings Adequate accessibility clearances for...

Страница 10: ...mm OUTLINE OF OUTER CASING 4 1 32 102mm 2 MIN 51mm FLOOR MOUNTING HOLE LOCATIONS VIEWED FROM FRONT OF HEATER Figure 8 SR 6 11 13 16 300mm 7 13 16 198mm 2 51 2 51 1 3 32 28mm 18 7 8 479mm 22 559mm OUTLINE OF OUTER CASING 4 1 32 102mm 2 MIN 51mm FLOOR MOUNTING HOLE LOCATIONS VIEWED FROM FRONT OF HEATER Figure 9 SR 10 18 457mm 14 356mm 2 51 2 51 1 3 32 28mm 18 7 8 479mm 22 559mm 4 1 32 MIN 102mm 2 1 ...

Страница 11: ...t Rock Wall 1 After locating mounting holes drill 4 5 16 8mm diameter holes into the wall 2 Insert 4 plastic expansion anchors provided into the holes 3 Tighten 4 10 x 1 25mm screws provided into the plastic expansion anchors Do not completely tighten screwheads to theplastic expansion anchors leave a1 8 3mm gap between screwheads and plastic expansion anchors 4 Mount heater onto the 4 screwheads ...

Страница 12: ...alled directly on carpeting tile or other combustible material other than wood flooring the appliance shall be installed on a metal or wood panel extending the full width and depth of the appliance Attention Optional Floor Stand meets requirement The base referred to above does not mean the fire proof base as used on wood stoves The protection is for rugs that are extremely thick and light colored...

Страница 13: ...above 2 Turn off all electric power to the appliance if appli cable 3 Push in manual gas control knob slightly and turn clockwise to OFF Do not force SR 18 KNOB SHOWN 4 Wait ten 10 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the safety information above If you don t smell gas go to the next step 5 Find pilot the pilot is attached at th...

Страница 14: ...dethecasingassembly and main burner assembly Use the following procedure to inspect the casing assembly and main burner assembly 1 Turn OFF gas supply to the heater 2 Turn OFF electric supply to the heater if optional blower is installed in heater 3 Remove lower louver from casing assembly 2 screws 4 Remove reflector from casing assembly 2 screws 5 Inspect interior of casing assembly for accumulat...

Страница 15: ...asp nut A with an open end wrench 2 Blow air pressure through the holes indicated by the arrows The main burner operation is MANUAL The owner must manually place the main burner in operation The owner will either select one three or five plaques to be in operation Once the owner has turned the main burner ON it will continue to operate until the owner manually turns the main burner OFF Description...

Страница 16: ... bracket with attached pilot away from main burner assembly do not damage pilot tubing 7 Disconnect supply tubing from orifice holder s 8 Remove orifice holder from venturi of main burner assembly 1 screw for each orifice holder 9 Remove main burner orifice from orifice holder Attention The number stamped on the main burner orifice is a millimeter diameter 10 As parts are being replaced in reverse...

Страница 17: ...6310 PILOT THERMOCOUPLE 11 R 6310 PILOT THERMOCOUPLE 12 SR 143 TUBING GAS VALVE TO PILOT 12 SR 143 TUBING GAS VALVE TO PILOT 13 SR 112 VALVE BRACKET 13 SR 112 VALVE BRACKET 14 R 2277 GAS VALVE COPRECI 14 R 2277 GAS VALVE COPRECI 15 SR 139 TUBING GAS VALVE TO BURNER 15 SR 139 TUBING GAS VALVE TO BURNER 16 SR 221 TUBING INLET REGULATOR TO GAS VALVE 16 SR 221 TUBING INLET REGULATOR TO GAS VALVE 17 R ...

Страница 18: ...1 27 SR 077 HEAT SHIELD 9 R 6308 PILOT ASSEMBLY LPG ONLY INCLUDES ITEMS 10 11 28 SR 120 OPTIONAL SRS 18 FLOOR STAND KIT 10 R 6309 SPARK IGNITOR 29 SR 121 OPTIONAL SRB 18 BLOWER KIT INCLUDES 29 THROUGH 36 11 R 6310 PILOT THERMOCOUPLE 30 R 1454 BRASS BUSHING 4 REQUIRED 12 SR 086 TUBING GAS VALVE TO PILOT 31 R 1499 RUBBER GROMMET 4 REQUIRED 13 SR 022 VALVE BRACKET 32 SR 195 BLOWER PAN 14 R 1649 GAS V...

Страница 19: ...16010 10 0314 Page 19 SR 6 PARTS VIEW ...

Страница 20: ...16010 10 0314 Page 20 SR 10 PARTS VIEW ...

Страница 21: ...16010 10 0314 Page 21 SR 18 PARTS VIEW ...

Страница 22: ...rranty parts All parts listed in the Parts List have a Part Number When ordering parts first obtain the Model Number and Serial Number from the name plate on your equipment Then determine the Part Number not the Index Number and the Description of each part from the fol lowing illustration and part list Be sure to give all this information Appliance Model Number Part Description Appliance Serial N...

Страница 23: ...using downward Place the bottom flange of the blower housing over the top edge of the top heat shield Insert the blower housing into the top portion of the heater by pivoting the blower housing upward 90 Attach the blower housing to the casing assembly with 4 screws provided with the optional blower 14 Grasp cord set at casing assembly back and pull excess cord set through casing assembly back Sec...

Страница 24: ...ill collect lint and could require periodic cleaning If the air output decreases or the noise level increases it indicates a dirty blower wheel To clean blower wheel 1 Turn OFF gas supply to the heater 2 Turn OFF electrical supply to the heater 3 Remove lower louver from casing assembly 2 screws 4 Remove reflector from casing assembly 2 screws 5 Remove upper louver from casing assembly 2 screws 6 ...

Страница 25: ...16010 10 0314 Page 25 APPLIANCE SERVICE HISTORY Date Dealer Name Service Technician Name Service Performed Notes ...

Страница 26: ...16010 10 0314 Page 26 APPLIANCE SERVICE HISTORY Date Dealer Name Service Technician Name Service Performed Notes ...

Страница 27: ...16010 10 0314 Page 27 APPLIANCE SERVICE HISTORY Date Dealer Name Service Technician Name Service Performed Notes ...

Страница 28: ...Remote Controls Thermostats Accessories and Parts Should any remote control thermostat accessory or other part fail because of defective workmanship within one year from the date of purchase Empire will repair or replace at Empire s option Duties of the Owner The appliance must be installed by a qualified installer and operated in accordance with the instructions furnished with the appliance A bil...

Отзывы: