Empire Heating Systems MV 120 Скачать руководство пользователя страница 10

Important: remove styrofoam inside front cover now.

Place the foam 

pads on the four raised “bumps” on the rear of the unit. 
These foam pads will protect the wall surfaces from 
damage.

Warning: the heater will not function properly if these 
connections are not tight and clean.

 Lighting Instructions

Connecting the gas supply

After connecting the gas supply to the gas control on the 
heater, the connections must be checked thoroughly for 
leaks. 

Remove the small piece of wood from the rear of the heater 
and discard. Four small adhesive foam pads are included with 
the unit and can be found in the accessory bag. 

Hang the heater on the arms on the wall support bracket, taking 
extreme care to ensure that the small diameter vent pipe fits 
inside the smaller opening in the rear of the unit. (See Figure 
9). The larger diameter vent pipe must then slide over the 
outside flange opening.

 Secure the unit to the 

wall support bracket with the two screws provided. 

Attach the

 to the back of the unit so that 

they may be read when necessary. These instructions are for 
current and future use. Make sure they remain accesible after 
the unit is installed.

Connect the gas supply to the 3/8” (9.5 mm) pipe on the lower 
part of the right side of the heater by using standard 
connectors. Please refer to the cautionary remarks noted in the 
beginning of this manual.

With the shut-off valve turned ON, but the gas control 

knob on the heater OFF, apply liberal amounts of a soapy water 
solution to all of the piping joints. A gas leak will cause 
bubbles to form. Note any leaks in the piping system, then shut 
off the gas at the shut-off valve, or at the gas meter or 
propane/LP tank serving the building. Fix the leaking joint and 
re-test the joints as directed above.

Once the supply is checked and does not leak, place the cover 
on the unit. See Figure 10. Be sure the foam packing has been 
removed. Secure the cover with the two nuts at the bottom of 
the unit which you had removed when unpacking.

eventual water filtration or the entrance of bugs is necessary. 

Press the flange against the outer wall surface and fasten the 
vent cap to the wall using the 4 screws (provided with the unit) 
in the holes prepared in the vent cap plate. Once the vent is 
secured to the wall, proceed filling the gaps between the vent 
plate and the wall with silicone sealing compound.

Inside the building, place the wall support plate (which is  
taped inside the cabinet during shipment) over the open end of 
the vent pipe and push the plate firmly against the interior wall.

Now level the plate with carpenter level and mark the 
mounting holes with a pencil (see Figure 8). Remove the wall 
support plate from the vent pipe and drill the two holes with the 
appropriate drill bit.

Place the wall support plate over the vent pipe again and affix 
the plate to the wall using the two screws provided with the 
unit.

You might need to handle the introduction of the larger 
pipe into the hole of the support plate with your fingers 
since the pipe could have suffered some minor 
deformation through the cutting process.   

Note: hollow wall fasteners (also supplied with the unit) 
are necessary for model MV 120. Models MV 130 and MV 
145 can be mounted on the wall studs.

Mounting the furnace

Take off the cover by loosening the two screws at the bottom. 
Pull the bottom away from the heater and lift it up off the tabs 
on top. 

INSTALLATION INSTRUCTIONS (cont.)

Figure 8

Figure 9

Figure 10

Page 10

MV1XX-1-0603

Содержание MV 120

Страница 1: ...ng Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier callthe fire department Installation and service must be performed by a qualified installer service agencyor thegassupplier This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for use with other ga...

Страница 2: ...duction Specifications Gas Supply Clearances Installation Instructions Lighting Instructions Pilot Flame Characteristics Main Burner Flame Characteristics Maintenance How to Order Repair Parts Parts List Parts View Troubleshooting PAGE 3 4 5 5 6 7 8 8 10 11 12 12 12 13 13 14 15 16 Page 2 MV1XX 1 0603 ...

Страница 3: ... e n q u e e s t á i n s t al a d o e l a p a r a t o L a r o p au o t r o s m a t e r i a l e s i n f l a m a b l e s n o d e b e n c o l o c a r s e e n ci m a o c e r c a d e e s t e a p a r a t o C u a l q u i e rp a n t a l l a d e s e g u r i d a d o pa n e l q u e s e a r e t i r a d o p a r a r e a l i z a re l s e r v i c i o d e l e q u i p o de b e s e r r e i n s t a l a d o a n t e s ...

Страница 4: ...odorlessand colorless You may not know all the following safety pre cautions which can protect both you and your family from an accident Read them carefully now then review them point by point with the members of your household Do not operate electric switches light matches use your phone Donotdoanythingthatcouldignitethegas Get everyone out of the building or area Do that IMMEDIATELY Closeall gas...

Страница 5: ... Any alteration of the original design installed other than as shown in these instructions or use with a type of gas not shownontherating plate is theresponsibility of theperson andcompanymakingthechange Important Notice Always consult your local Building Department regarding regulations codes or ordinances which apply to the installation of adirectventwallfurnace 1 Installer must leave instructio...

Страница 6: ...2 61kPa Propanegas models will have a manifold pressure approximately 10 0 w c 2 49kPa at the valve outlet with the inlet pressure to the valvefromaminimumof11 0 w c 2 739kPa forthepurpose of input adjustment to a maximum of 13 0 w c 3 237kPa A 1 8 3mm N P T plugged tapping accessible for test gauge connection islocatedontheoutletside ofthegascontrol LocatingGas Supply Recommended Gas Pipe Diamete...

Страница 7: ...nter of theventcaptothe nearestoutsidecornerorobstruction is 16 407mm 5 The MV 120 MV 130 and MV 145 minimum wall depth is 4 1 2 114 mm and the maximum is 12 305 mm The Figure 3 Vent terminal clearances A A G C F L D E B A B C D E F G H I clearance above grade veranda porch deck or balcony clearance to window or door that may be opened clearance to permanently closed window vertical clearance to v...

Страница 8: ...nttheunittobemounted A full scale template is furnished with the unit which illustrates the vent and gas supply openings and mounting holesintheir correctlocationsonthewall the figure 4 gives the required dimensions for mounting theunit intheeventthatthe templateisunusableorlost Place the template on the wall so that the vent opening will be located between the studs and in the case of the MV 130 ...

Страница 9: ...comes through the wall It is not where you willcutthepipes It is very important that this be a clean straight cut for the heatertoperformproperly Remember to remove the vent assembly from the wall in ordertocut thetubes Installingtheventassemblyandwallsupportplate the indicated diameter in both walls and cut them Your hole will be about 1 to 2 26 to 52 mm depending on the unit model larger indiame...

Страница 10: ...valve or at the gas meter or propane LPtankserving thebuilding Fixtheleaking jointand re testthejoints as directedabove Once the supply is checked and does not leak place the cover on the unit See Figure 10 Be sure the foam packing has been removed Secure the cover with the two nuts at the bottom of theunitwhich youhadremovedwhenunpacking eventualwaterfiltrationortheentranceofbugsisnecessary Press...

Страница 11: ...he gas control knob counter clockwise to the PILOT position Depress the gas control knob and push in the Piezo igniter several times until the pilot is lit The pilot flame can be observed by looking down the inside of the heater jacket A small reflector on the right hand side near 1 Setthethermostatto lowestsetting 2 Openthe controlaccess panelonthetop rightside oftheunit 3 Turn the gas knob clock...

Страница 12: ...in thesupplypipingleading to theappliance ifinstalled or at the gas meter or propane LP tank 3 Remove the two screws which hold the unit to the wall supportplateandliftandpulltheunitawayfromthewall 4 Carefully examine the interior of the vent pipes both large and small diameter If you notice any blockage or obstruction cleanthepipes 5 Look insidetheopenings of the rear oftheunitandcheckfor any for...

Страница 13: ...ine with a soapy water solution Bubbles on any of the joints indicated a leak is present and must be repaired Turn OFF the gas to the unit when performing any repairs to the gas piping system After the pilot lines are checked turn the main burner ON and again check all joints in the piping system for leaks with soapy water Repair any joints which indicate a leak ispresent 12 While the main burner ...

Страница 14: ...43018500 SD430185B0 SD442202B0 SK00000048 SK00000051 SD44107500 SD44105800 SD44305500 SD44177000 SD44176900 SD44175800 SD44120800 SA00000263 SD44107002 SD44107100 SD44106900 SD44106801 SK00000053 SK00000054 SD44106100 SD44158001 SD44158102 SD44125500 SD44125200 SD443332C0 SD443332D0 SD44111300 SD44132400 SD44152900 SD44153000 SK00000055 PART MV 145 N SD43018400 SD430184B0 SD44326100 SK00000049 SK0...

Страница 15: ...Page 15 PARTS VIEW MV1XX 1 0603 ...

Страница 16: ...ning thesmallbrassscrewonthelefthand fronttop of the gas control top plate Backing the screw out counterclockwise increases the pilot flame The pilot flame should contact the thermocouple tip but not excessively long SeeLightingInstructions the thermocouple is a standard 24 millivolt probe Check its effectiveness by removing it from the heater and attach a probe alligator clip to themagnetcontactb...

Отзывы: