Page 8

VFHS-20/10

GAS SUPPLY

Check all local codes for requirements, especially for the size and
type of gas supply line required.

Recommended Gas Pipe Diameter

Pipe Length

Schedule 40 Pipe

Tubing, Type L

(Feet)

Inside Diameter

Outside Diameter

Nat.

L.P.

Nat.

L.P.

0-10

1/2"

3/8"

1/2"

3/8"

1.3 cm

1.0 cm

1.3 cm

1.0 cm

10-40

1/2"

1/2"

5/8"

1/2"

1.3 cm

1.3 cm

1.6 cm

1.3 cm

40-100

1/2"

1/2"

3/4"

1/2"

1.3 cm

1.3 cm

1.9 cm

1.3 cm

100-150

3/4"

1/2"

7/8"

3/4"

1.9 cm

1.3 cm

2.2 cm

1.9 cm

Note: Never use plastic pipe. Check to confirm whether your local
codes allow copper tubing or galvanized.

Note: Since some municipalities have additional local codes, it is
always best to consult your local authority and installation code.

Installing a New Main Gas Cock
Each appliance should have its own manual gas cock.
A manual main gas cock should be located in the vicinity of the
unit. Where none exists, or where its size or location is not
adequate, contact your local authorized installer for installation or
relocation.

Compounds used on threaded joints of gas piping shall be resistant
to the action of liquefied petroleum gases. The gas lines must be
checked for leaks by the installer. This should be done with a soap
solution watching for bubbles on all exposed connections, and if
unexposed, a pressure test should be made.

Never use an exposed flame to check for leaks. Appliance must
be disconnected from piping at inlet of control valve and pipe
capped or plugged for pressure test. Never pressure test with
appliance connected; control valve will sustain damage!

A gas valve and ground joint union should be installed in the gas
line upstream of the gas control to aid in servicing. It is required
by the National Fuel Gas Code that a drip line be installed near the
gas inlet. This should consist of a vertical length of pipe tee
connected into the gas line that is capped on the bottom in which
condensation and foreign particles may collect.

The use of the following gas connectors is recommended:
— ANS Z21.24 Appliance Connectors of Corrugated Metal

Tubing and Fittings

— ANS Z21.45 Assembled Flexible Appliance Connectors of

Other Than All-Metal Construction

The above connectors may be used if acceptable by the authority
having jurisdiction.

Pressure Testing of the Gas Supply System
1.

To check the inlet pressure to the gas valve, a 1/8" (3mm)
N.P.T. plugged tapping, accessible for test gauge connection,
must be placed immediately upstream of the gas supply
connection to the appliance.

2.

The appliance and its individual shutoff valve must be
disconnected from the gas supply piping system during any
pressure testing of that system at test pressures in excess of
1/2 psig (3.5 kPa).

3.

The appliance must be isolated from the gas supply piping
system by closing its individual manual shutoff valve during
any pressure testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig (3.5 kPa).

Figure 3

Attention! If one of the above procedures results in pressures in
excess of 1/2 psig (14" w.c.) (3.5 kPa) on the appliance gas valve,
it will result in a hazardous condition.

Checking Manifold Pressure
VFHS-20R  
Natural gas will have a manifold pressure of
approximately 3.5" w.c. (.871kPa) for maximum input or 1.7"
w.c. (.423kPa) for minimum input at the pressure regulator outlet
with the inlet pressure to the pressure regulator from a minimum
of 4.5" w.c. (1.120kPa) for the purpose of input adjustment to a
maximum of 10.5" w.c. (2.614kPa). VFHS-20/10T Natural gas
will have a manifold pressure of approximately 6.0" w.c. (1.49kPa)
at the pressure regulator outlet with the inlet pressure to the
pressure regulator from a minimum of 7.0" w.c. (1.74kPa) for the
purpose of input adjustment to a maximum of 10.5" w.c.
(2.615kPa). VFHS-20R Propane gas will have a manifold pressure
approximately 10.0"w.c. (2.49kPa) for maximum input or 6.3"w.c.
(1.568kPa) for minimum input at the pressure regulator outlet
with the inlet pressure to the pressure regulator from a minimum
of 11.0"w.c. (2.739kPa) for the purpose of input adjustment to a
maximum of 13.0"w.c. (3.237kPa). VFHS-20/10T Propane gas
will have a manifold pressure approximately 10.0"w.c. (2.49kPa)
at the pressure regulator outlet with the inlet pressure to the
pressure regulator from a minimum of 11.0"w.c. (2.739kPa) for
the purpose of input adjustment to a maximum of 13.0"w.c.
(3.237kPa).

Содержание VFHS-10T-1

Страница 1: ...nstructions If you cannot reach your gas sup plier call the fire department Installation and service must be per formedbyaqualifiedinstaller service agency or the gas supplier This is an unvented gas...

Страница 2: ...11 Log Placement 12 Placement of Glowing Embers Rock Wool 12 Operation Instructions Flame Appearance 13 VFHS 20R Lighting Instructions 14 VFHS 20 10T Lighting Instructions 15 Pilot Flame Characterist...

Страница 3: ...high surface temperature and should stay away to avoid burns or clothing ignition Young children should be carefully supervised when they are in the same room with the appliance Do not place clothing...

Страница 4: ...service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption on walls of ne...

Страница 5: ...d at the rate of 4 percent for each 1 000 feet 305m above sea level Contact the manufacturer or your gas company before changing spud orifice size Instructions to Installer 1 Installer must leave inst...

Страница 6: ...regate input rating of all appliances installed in that space Rooms communicating directly with the space in which the appliances are installed through openings not furnished with doors are considered...

Страница 7: ...t the space is an unconfined space You will need no additional fresh air ventilation WARNING You must provide additional ventilation air in a confined space VENTILATION AIR Ventilation Air From Inside...

Страница 8: ...Z21 45 Assembled Flexible Appliance Connectors of Other Than All Metal Construction The above connectors may be used if acceptable by the authority having jurisdiction Pressure Testing of the Gas Supp...

Страница 9: ...lace opening to any combustible wall or material should not be less than 4 inches 2 Clearances from the top of the fireplace opening to the ceiling should not be less than 30 inches Mantel Clearances...

Страница 10: ...astboard into right mantel side Breastboard will rest on fireplace top and in front of nailing flange Attention Placing the breastboard in front of nailing flange will secure the fireplace 6 Placeleft...

Страница 11: ...two 2 10 x 1 2 screws for each nailing flange 2 Gas line connections must be made at this time When facing the appliance the gas supply will enter on right hand side See Gas Supply Page 8 3 Insert fi...

Страница 12: ...rear portion of burner A thin layer of rock wool should be placed under open space between the right and left middle logs Rock wool should not be placed in the area of the pilot assembly 1 Remove shi...

Страница 13: ...Do not place a blower inside the burner area of the firebox Ceiling fans may create drafts that alter flame patterns Sooting and improper burning will result During manufacturing fabricating and ship...

Страница 14: ...le Turn ON OFF switch to OFF position and or set thermostat if present to lowest setting If appli cable Turn off all electric power to the heater 1 STOP Read the safety information label 2 Make sure t...

Страница 15: ...ot force TO TURN OFF GAS TO APPLIANCE 1 Set thermostat gas control knob to lowest setting 2 Turn off all electric power to appliance if service is to be performed if applicable LIGHTING INSTRUCTIONS 7...

Страница 16: ...ect appearance of pilot flame Figure 17 If pilot flame pattern is incorrect as shown in Figure 17 See Troubleshooting page 19 Cleaning and Maintenance Pilot Oxygen Depletion Sensor Pilot Figure 18 Whe...

Страница 17: ...orifice fitting 8 Remove air shutter from orifice fitting 9 ForNaturalgasonly remove20 000Btumainburnerorifice marked 49 from orifice fitting and replace with 10 000 Btu VFHS 20R Main Burner Operatio...

Страница 18: ...k Red wires to attach optional components Check 750 Millivolt System Operation Millivolt system and all individual components may be checked with a millivolt meter 0 1000 MV range Remote Receiver Use...

Страница 19: ...t assembly or get it serviced g Gas regulator setting is not correct Replace gas regulator 7 ODS pilot lights but flame goes out when control knob is released a Control knob not fully pressed in Press...

Страница 20: ...COVER PLATE 37 R 3436 REMOTE OFF ON SWITCH NOT SHOWN 11458 TUBING VALVE TO PILOT NOT SHOWN 11459 TUBING VALVE TO BURNER NOT SHOWN R 4579D SWITCH WIRE HARNESS NOT SHOWN P 263 NIPPLE 7 1 2 VFHS 20 10T...

Страница 21: ...Page 21 VFHS 20 10 PARTS VIEW...

Страница 22: ...ges of the 2 side brick liners Attach liner mounting brackets to outer casing with 4 four 10 x 1 2 screws provided in optional brick liner kit 6 Replace logs into burner assembly Refer to Log Placemen...

Страница 23: ...itemotor Startone 1 8x1 2 Phillipsscrewinto top motor mounting bracket and gasket adjacent to motor Align and attach blower assembly to outer casing side See Figure 2 10 Snap Heyco into blower shield...

Страница 24: ...INSTRUCTIONS continued Figure 3 Figure 4 cover on burner assembly Insert blower shield front adjacent to blower motor and blower shield side Align clearance hole on blower shield front with left fron...

Страница 25: ...Step 6 Tighten two 2 10 x 1 2 screws at interior top of inner casing that were loosened in Step 6 28 Attach burner assembly to inner bottom with three 3 10 x 1 2 screws from Step 5 29 Attach rear log...

Страница 26: ...liance cord plug can be plugged into the adapter and be electrically grounded CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous oper...

Страница 27: ...5 REMOTE CONTROL 2 R 3486 EXTENSION CORD 3 R 3487 CONTROL UNIT FRBTC 1 BATTERY OPERATED REMOTE CONTROL WITH THERMOSTAT 1 R 3516 REMOTE CONTROL 2 R 3517 REMOTE CONTROL HOLDER 3 R 3518 CONTROL UNIT FRBC...

Страница 28: ...Page 28 VFHS 20 10 SERVICE NOTES Empire Comfort Systems Inc Nine Eighteen Freeburg Ave Belleville Illinois 62222 0529 Web Site www empirecomfort com E mail info empirecomfort com...

Отзывы: