background image

26996-7-0411

Page 21

With proper installation and maintenance, your new Direct vent Gas Fireplace will provide years of trouble-free 

service. If you do experience a problem, refer to the Trouble Shooting Guide below. This guide will assist a qualified 

service person in the diagnosis of problems and the corrective action to be taken.

1.  Spark ignitor will not light pilot after repeated triggering 

of piezo ignitor button.

a.  Defective ignitor (no spark electrode) 

 

—Check for spark at electrode and pilot; if no spark and 

electrode wire is properly connected, replace ignitor.

b.  No gas or low gas pressure.

 

—Check  remote  shut  off  valves  from  fireplace.  Usually 

there is a valve near the main. There can be more than 

one (1) valve between the fireplace and main.

 

—Low pressure can be caused by a variety of situations 

such as a bent line, too narrow diameter of pipe, or low 

line pressure. Consult with plumber or gas supplier.

c.  No LP in tank. 

  —Check LP (propane) tank. Refill tank.

2.  pilot  will  not  stay  lit  after  carefully  following  lighting 

instructions.

a.  Defective thermocouple.

 

—Check that pilot flame impinges on thermocouple. Clean 

and/or adjust pilot for maximum flame impingement.

 

—Ensure the thermocouple connection at the gas valve 

is fully inserted and tight (hand tight plus 1/4 turn). Faulty 

thermocouple if reading is below specified minimum of 15 

millivolts.

 

—Disconnect the thermocouple from the valve, place one 

millivolt meter lead wire on the end of the thermocouple 

and the other millivolt meter lead wire on the thermocouple 

copper wire. Start the pilot and hold the valve knob in. If 

the millivolt reading is less than 15 millivolt, replace the 

thermocouple.

b.  Defective valve.

 

—If thermocouple  is producing  more than 15 millivolts, 

replace faulty valve.

3.  pilot burning, no gas to burner, valve knob “ON”, REMOTE/

OFF/ON switch “ON.”

a.  REMOTE/OFF/ON switch, wall switch, remote control or 

wires defective.

 

—Check REMOTE/OFF/ON switch and wires for proper 

connections. Place jumper wires across terminal at switch. 

If burner comes on, replace defective switch. If OK, place 

jumper wires across switch wires at gas valve-if burner 

comes on, wires are faulty or connections are bad.

b.  Thermopile may not be generating sufficient millivolts.

 

—If the pilot flame is not close enough physically to the 

thermopile, adjust the pilot flame.

 

—Be sure the wire connections from the thermopile at the 

gas valve terminals are tight and the thermopile is fully 

inserted into the pilot bracket.

 

—Check the thermopile with a millivolt meter. Take the 

reading at TH-TP & TP terminals of the gas valve. The 

meter should read 350 millivolts minimum, while holding the 

valve knob depressed in the PILOT position, with the pilot 

lit, and the REMOTE/OFF/ON switch in the OFF position. 

Replace the faulty thermopile if the reading is below the 

specified minimum. 

 

—With the pilot in the ON position, disconnect the thermopile 

leads from the valve. Take a reading at the thermopile leads. 

The reading should be 350 millivolts minimum. Replace 

the thermopile if the reading is below the minimum.

c.  Defective valve.

 

—Turn valve knob to ON. Place REMOTE/OFF/ON switch 

to ON. Check with millivolt meter at thermopile terminals. 

Millivolt meter should read greater than 200 millivolts. If 

the reading is okay and the main burner does not ignite, 

replace the gas valve.

d.  Plugged main burner orifice.

 

—Check main burner orifice for blockage and remove.

4.  Frequent pilot outage problem.

a.  Pilot flame may be too high or too low, or blowing (high), 

causing pilot safety to drop out.

 

—Clean and adjust flame for maximum flame impingement 

on  the  thermocouple.  Follow  lighting  instructions 

carefully.

5.  The pilot and main burner extinguish while in operation.

a.  No LP (Propane) in tank. 

 

Check LP (Propane) tank. Refill fuel tank.

b.  Inner vent pipe leaking exhaust gases back into system.

 

—Check for leaks.

c.  Glass too loose, gasket leaks in corners after usage.

 

—Be certain glass assembly is installed correctly.

d.  Horizontal vent improperly pitched.

 

—The horizontal vent cap should slope down only enough 

to prevent any water from entering the unit. The maximum 

downwards slope is 1/4 inch.

e.  Bad thermopile or thermocouple.

 

—Replace if necessary.

f.  Improper vent cap installation.

 

—Check for proper installation and freedom from debris 

or blockage.

6.  Glass soots, and/or soot deposits collected on logs.

a.  Flame impingement on logs incorrect.

 

—Check and adjust log position. See Page 17. Contact 

Empire Comfort Systems, Inc.

b.  Debris around throat of main burner.

 

—Inspect the opening at the base of the main burner. It is 

imperative that NO material be placed in this opening.

7.  Flame burns blue and lifts off main burner.

a.  Insufficient oxygen being supplied.

 

—Check to make sure vent cap is installed properly and 

free of debris. Make sure that vent system joints are tight 

and have no leaks.

 

—Check to make sure that no material has been placed 

at the main burner base.

STANDING pILOT TROUBLESHOOTING

Содержание DV25IN33L(N

Страница 1: ...sed GAS FIRED Installer Leave this manual with the appli ance Consumer Retain this manual for future refer ence Do not store or use gasoline or other flam mable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier fro...

Страница 2: ...nation 13 Alternate ON OFF Switch Installation 14 Surround Panel Installation 15 Blower Accessory Information 16 Log Placement 17 Operating Instructions 18 Standing Pilot Lighting Instructions 19 Standing Pilot Wiring 20 Standing Pilot Troubleshooting 21 Insert Maintenance and Service 22 Decorative Accessories 23 Insert Parts View 24 Insert Parts List 25 Master Parts Distributor List 26 How To Ord...

Страница 3: ... glass front or any part removed for servicing the appliance must be replaced prior to operating the appliance Work should be done by a qualified service person Keep burner and control compartment clean Vent cap is hot while fireplace is in operation Installation and repair should be done by a qualified service person The appliance shouldbeinspectedbeforeuseandatleastannually by a qualified servic...

Страница 4: ...perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption on walls of new cylinders and tanks is possible Therefore people should be particularly alert and careful when new tanks or cylinders are placed in service Odor fade can occur in new tanks or reinstalled ol...

Страница 5: ...h the National Fuel Gas Code ANSI Z223 1 NFPA 54 Natural Gas and Propane Installation Code or CSA B149 1 in Canada Available from theAmerican National Standards Institute Inc 11 West 42nd St New York N Y 10036 Any alteration of the original design installed other than as shown in these instructions or use with a type of gas not shown on the rating plate is the responsibility of the person and comp...

Страница 6: ...himney pipe DVVK3FV Vertical Vent Kit 25 Two pieces of 25 FlexVent Rectangle Cap Flashing connectors and clamps Recommended when installing to a square or rectangular clay flue DVK35 Vent Extension Kit 35 flex vent extension section with 2 connectors and 4 clamps NOTICE When installing vent caps special locally made flashings may be required to properly seal the vent system to the existing chimney...

Страница 7: ... 28 14 1 2 11 1 8 25 1 4 12 3 4 17 18 5 16 27 6 3 4 9 20 25 5 8 40 DV33IN 22 3 4 31 16 14 1 8 28 1 4 14 1 4 18 3 4 21 5 16 30 8 1 4 10 1 2 21 1 2 28 5 8 43 DV35IN 24 3 4 34 16 16 1 8 31 1 4 14 1 4 21 3 4 23 5 16 33 8 1 4 10 1 2 23 30 5 8 46 A D C B Figure 2 Fireplace Opening Dimensional Information Sizing MINIMUM FIREPLACE OPENING DIMENSIONS MODEL NO HEIGHT A FRONT WIDTH B DEPTH C REAR WIDTH D DV2...

Страница 8: ...tation of any type should be placed on or attached to the fireplace The flow of heat can ignite combustibles Figure 4 8 MINIMUM CLEARANCE TO PERPENDICULAR COMBUSTIBLE SIDE WALL FROM EDGE OF DOOR FRAME Figure 3 Distance from Face of Fireplace Height Above Top of Insert A 10 N 23 B 9 1 4 O 22 C 8 3 4 P 21 D 8 Q 20 E 7 1 4 R 19 F 6 1 2 S 18 G 6 T 17 H 5 1 4 U 16 I 4 1 2 V 15 J 3 3 4 W 14 K 3 X 13 L 2...

Страница 9: ...one of the procedures results in pressures in excess of 1 2 psig 14 w c 3 5 kPa on the fireplace gas valve it will result in a hazardous condition Checking Manifold Pressures Both Propane and Natural gas valves have a built in pressure regulator in the gas valve Natural gas models will have a manifold pressure of approximately 3 5 w c 871kPa at the valve outlet with the inlet pressure to the valve...

Страница 10: ...grill area should be left open NOTICE Surround panel kits have been tested and approved to cover existing air circulation vents or grills NOTICE Cutting of sheet metal parts of a fireplace in order to install the fireplace insert is prohibited WARNING Only the surround as supplied may be used to cover inte gral grills on the solid fuel burning fireplace No other com ponents such as shrouds sheet m...

Страница 11: ...o a zero clearance factory built wood burning fireplace the use of the DVKI Round Vertical Termination Kit should allow you to mount the vent adaptor and cap to the exposed round chimney pipe easily Connecting the Vent Pipe CAUTION Sharp edges Always use gloves when installing Install the 3 inch flexible vent pipes down through the chimney Attach the pipe to cap adaptor to the termination cap and ...

Страница 12: ...ENT CONNECTION RETAINER SCREWS MAY BE INSTALLED THROUGH THE VENT CLAMPS TO ENSURE POSITIVE SECUREMENT OF VENTING SCREWS ADDED THROUGH VENT CLAMPS TO RETAIN VENTING TO COLLARS RECOMMENDED USE HIGH TEMP SEALANT ON VENT CONNECTIONS USE HIGH TEMP SEALANT ON VENT CONNECTIONS ROUND TERMINATION CAP DVKI KIT ROUND CO LINEAR TO CO AXIAL ADAPTOR BLOWER ACCESS COVER PLATE BLOWER POWER CORD OPTIONAL LOW VOLTA...

Страница 13: ...pping out at joints or seams Condensate can cause corrosion of caps pipe and fittings It may be caused by having excessive lateral runs or having exterior portions of the system exposed to cold weather 4 Inspect joints to verify that no pipe sections or fittings have been disturbed and consequently loosened Also check mechanical supports such as wall straps or plumbers tape for rigidity Determinin...

Страница 14: ...und panel assembly against the face of the insert and align the lower retaining tabs with the notches on the insert sides Lift the surround panel assembly slightly until the bot tom return flange top panel is positioned over the top flange on the insert This secures the surround panel assembly to the insert without screws Traditional Cast Iron Surrounds WIRING FROM MILLIVOLT GAS VALVE ON OFF SWITC...

Страница 15: ...N FINISHING THE FIREPLACE INSERT NEVER OB STRUCT OR MODIFY THE AIR INLET OUTLET LOUVERS ON THE FIREPLACE INSERT IN ANY MANNER NOTE INSTALL SURROUND PANELS SO THAT THE TOP PANEL RETURN FLANGE SLIDE S OVER THE TOP FLANGE ON THE INSERT 1 Ref SURROUND PANEL ASSEMBLY ENGAGE SIDE PANEL HOOKS WITH THE NOTCHES PROVIDED ON THE SIDE FLANGES Figure 14 Figure 15 ...

Страница 16: ...BTU input level setting control by adjustment of the HI LO knob located on the gas valve Blower removal instructions Servicing or removal of the blower system must be performed by a qualified service person If the blower assembly Item 45 page 24 must be replaced the following steps are recommended for removal 1 Turn off gas and disconnect the electrical supply 2 Remove the glass door assembly 3 Re...

Страница 17: ...the firebox on top of the rear log support NOTICE DV25IN models incorporate two small tabs in the rear log support that keep the back log positioned correctly DV33IN models have one small tab in the rear log support to ensure the back log is in the correct position The DV35IN models will have two tabs bent forward in the rear log support to ensure proper left to right positioning of the log plus o...

Страница 18: ...nutes before you turn the gas control knob from the PILOT position to the ON position This time period allows the millivolts electrical current to build up to a sufficient level allowing the gas control to operate properly 1 FollowtheSAFETYandLIGHTINGINSTRUCTIONSforstanding pilot controls found in this manual and on labels found in control compartment behind the door assembly WARNING During the in...

Страница 19: ...F ON switch to desired setting FOR YOUR SAFETY READ BEFORE LIGHTING Warning If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life A This appliance has a pilot which must be lighted by hand When lighting the pilot follow these instructions exactly B Before lighting smell all around the appliance area for gas Be sure to...

Страница 20: ...O THE WALL SWITCH OR THE CONTROL VALVE WILL BE DESTROYED WARNING LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROL WIRING ERRORS CAN CAUSE IM PROPER AND DANGEROUS OPERATION VERIFY PROPER OPERATION AFTER SERVICING For Standing Pilot Ignition Wiring Appliance Requirements WARNING DO NOT CONNECT 110 120 VAC TO THE GAS CONTROL VALVE OR THE APPLIANCE WILL MALFUNCTION AND THE VALVE WILL BE D...

Страница 21: ...tions from the thermopile at the gas valve terminals are tight and the thermopile is fully inserted into the pilot bracket Check the thermopile with a millivolt meter Take the reading at TH TP TP terminals of the gas valve The metershouldread350millivoltsminimum whileholdingthe valve knob depressed in the pilot position with the pilot lit and the REMOTE OFF ON switch in the OFF position Replace th...

Страница 22: ...re that no debris is interfering with the flow of air Inspect entire vent system for proper function Cleaning Logs Use a soft brush attachment on a vacuum cleaner to gently remove dust or soot deposits from logs and burner Cleaning Glass Door Frequency After the first 3 to 4 hours of use As necessary after initial cleaning By Home owner Task Remove and clean glass after the first 3 to 4 hours of u...

Страница 23: ...ormation beyond what your dealer can furnish contact Empire Comfort Systems Inc Nine Eighteen Freeburg Ave Belleville Illinois 62220 Black Gold Finish Hammered Pewter Brushed Stainless Black Gold Finish Hammered Pewter Brushed Stainless Black Gold Finish Hammered Pewter Brushed Stainless Black Black Black Black Black Standard Gold Finish Hammered Pewter Brushed Stainless Black Used to finish off b...

Страница 24: ...26996 7 0411 Page 24 INSERT PARTS VIEW 14 34 35 36 37 38 39 40 41 42 44 47 46 11 10 5 7 8 32 33 32 4 6 7 45 43 1 2 3 1 9 17 19 18 22 23 31 21 24 20 13 26 27 30 29 28 15 30 16 25 12 48 ...

Страница 25: ... LP 20 R9189 R9189 R9189 GASKET PILOT 21 R5676 R5676 R5676 AIR SHUTTER 22 P253 P253 P253 FITTING ORIFICE ANGLED 23a P286 P243 P244 ORIFICE MAIN BURNER NAT 23b P214 P250 P210 ORIFICE MAIN BURNER LP 24 23311 25541 25541 BURNER ASSEMBLY 25 22959 22959 22959 VALVE BRACKET 26 22739 22738 22738 TUBING ASSEMBLY 27 22973 22973 22973 SHIELD VALVE 28a R7577 R7577 R7577 VALVE SIT GAS NAT 28b R7578 R7578 R757...

Страница 26: ...treet Hartford CT 06114 Phone 860 722 2433 Toll Free 800 243 9360 Fax 860 293 0479 Toll Free Fax 800 274 2004 Websites www fwwebb com www victormfg com Parts Heater Hearth and Grills MASTER PARTS DISTRIBUTOR LIST Parts Not Under Warranty Parts can be ordered through your Service Person Dealer or a Master Parts Distributor See this page for the Master Parts Distribu tors list For best results the s...

Страница 27: ...26996 7 0411 Page 27 APPLIANCE SERVICE HISTORY Date Dealer Name Service Technician Name Service Performed Notes ...

Страница 28: ...ms Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question please contact your dealer www empirecomfort com ...

Отзывы: