Page 35
Installation and Operation Manual - Gateway 2300
ENGLISH
D) Clearance along the bottom of the shield: minimum 1" (25 mm) and maximum 3" (75 mm).
E) Minimum clearance along the top of the shield at the ceiling: 3" (75 mm).
F) Mounting hardware must not be located closer than 8" (200 mm) from the vertical centre line of
the appliance.
G) Edge clearance for ceiling shields to side and back walls: 3" (75 mm).
H) Shield extension beyond each side of the appliance: 18" (450 mm).