INSTALLATION PREPARATIONS
IMPORTANT!
•
Iflongductrunisneeded,increasetheductsize
from 6" to 7" or 8" to 9".
•
Ifareducerisneeded,usealongreducerinsteadof
apancakereducerandinstallitasfarawayfromthe
rangehoodaspossible.Reducingtheductsizewill
restrict and decrease the speed of the airflow and
hense lower the range hood's performance.
•
If transitions or turns are needed, install them as far
away fromthe range hood as possibleand keep the
distance between the 2 as far apart as possible.
•
The minimum mounting height should be no less
than 24" and the maximummounting height should
be no more than 30".
•
Also refer to the owner's manual of the stove
topfortheheight clearancerequirementandthe
recommended mounting height above the range.
Note
•
It is important to install the range hood at the proper
mounting height. Hoods mounted too low could result
in heat damage and fire hazard while hoods mounted
toohighwillbeoutofreachandhensereduceits
performance andefficiency.
Minimum Duct Size:
•
Round: 6" minimum.
•
Rectangular: 3-1/4" x 10" minimum.
Product Dimension
IMPORTANT!
Observe all governing codes and ordinances.
It is the customer's responsibility:
•
Tocontact a qualified electrical installer;
•
To ensure that the electrical installation is in
compliance with applicable codes and standards.
Electrical Requirements:
•
A 120V, 60Hz., AC only, 15A fused electrical circuit is
required.
•
Wiresizesandconnectionsmustconformwiththe
power rating of the range hood and all applicable
codes and standards.
•
DO NOT have a fuse in the neutral or ground circuit.
•
The 3-prong outlet should be grounded. If the
powercordplugisnotused,thepowercord’sgreen
wire should be connected to ground. Check with
aqualified electrician if you are not surethat the
range hood is properly grounded.
•
DO NOT ground to a gas pipe.
•
Therangehoodmustbeconnectedwithcopper
wire/plug only.
•
Therangehoodshouldbeconnecteddirectlytothe
fuseddisconnect box(orcircuit breaker)through
flexiblearmoredornon-metallicsheathedcopper
cable. ETLlisted strain relief must be provided at
each end of the power supply cable.