1. DESCRIZIONE DEI COMPONENTI
GB
GB
9. FUNCTIONAL ANOMALIES
Parameter
number
Description
Observation
0
Normal display
Compressor frequency or fault code
1
Number of connected internal units
2
Operating Modes of the Outdoor Unit
0 = Stand-by, 1 = Ventilation, 2 = Cooling, 3 = Heating, 4 = forced cooling, 5 =
forced defrosting
3
Internal Unit Power A
The unit of measure is the power horses, so it will be displayed: "– –"
= No units; "0.8"=7kBtu; "1"=9kBtu; "1.2"=12kBtu; "1.5"=18kBtu;
4
Power output to internal unit B
5
Power delivered to internal unit C
6
Power delivered to indoor unit D
7
Power output to internal unit E
8
Required power to indoor unit A
The unit of measure is the power horses, so it will be displayed: "– –"
= No units; "0.8"=7kBtu; "1"=9kBtu; "1.2"=12kBtu; "1.5"=18kBtu;
9
Required power to internal unit B
10
Required power to indoor unit C
11
Required power to indoor unit D
12
Required power to the indoor unit E
13
Total power required by internal units
14
Frequency corresponding to the total power demanded by
the indoor units
15
Frequency after the limitation
16
Frequency required for the compressor
17
Internal unit exchanger output temperature A (T
2B
A)
If the temperature is below -9 ° C, "-9" will still be displayed.
If the temperature is above 70 ° C, "70" will still be displayed.
If the indoor unit is not connected, "- -"
18
Internal unit exchanger output temperature B (T
2B
B)
19
Internal unit exchanger output temperature C (T
2B
C)
20
Internal unit exchanger output temperature D (T
2B
D)
21
Internal unit exchanger output temperature E (T
2B
E)
22
Ambient Indoor Unit Temperature A (T
1
A)
If the temperature is below -9 ° C, "-9" will still be displayed.
If the temperature is above 70 ° V, "70" will still be displayed.
If the indoor unit is not connected, "- -"
23
Ambient Indoor Unit Temperature B (T
1
B)
24
Ambient Indoor Unit Temperature C (T
1
C)
25
Ambient Indoor Unit Temperature D (T
1
D)
26
Ambient Indoor Unit Temperature E (T
1
E)
27
Internal unit evaporator temperature A (T
2
A)
If the temperature is below -9 ° C, "-9" will still be displayed.
If the temperature is above 70 ° C, "70" will still be displayed.
If the indoor unit is not connected, "- -"
28
Internal unit evaporator temperature B (T
2
B)
29
Internal unit evaporator temperature C (T
2
C)
30
Internal unit evaporator temperature D (T
2
D)
31
Internal unit evaporator temperature E (T
2
E)
32
External unit exchanger temperature (T3)
33
Outdoor ambient temperature (T4)
34
Compressor exhaust temperature (T5)
The displayed value is between 30 and 129 ° C.
If the temperature is below 30 ° C, "30" will still be displayed.
If the temperature is higher than 99 ° C, only the last two digits will be display-
ed (eg 105 ° C will be displayed "0.5").
35
Current value
The display value is a hexadecimal number. For example, if the display shows
"Cd", it means 205.
36
Current value
37
Inner expansion valve opening rate A
If the value is greater than 99, only the last two digits will be displayed.
Actual opening degree = value at display x 4.
For example, if you see "2.0" it means the opening is 120 x 4 = 480p.
38
Inner expansion valve opening rate B
39
Inner expansion valve opening rate C
40
Inner expansion valve opening rate D
41
Inner expansion valve opening rate E
Parameters displayed