11
GB
GB
The two air conditioner units are connected to each other by means of copper
piping. A maximum of 10 curves is allowed and beyond this number the correct
operation and the declared yield of the air conditioner are not guaranteed.
The two units can be positioned with a maximum gradient of 5 metres.
In cases where the indoor unit is installed higher than the outdoor unit with:
Between 3 and 5 meters must be provided an intermediate siphon to lock oil.
Warning!
Both pipe-lines must be provided with siphon.
A
D
E
C
B
1/2
1/2
Outdoor Unit
Indoor Unit
A (mm)
B (mm)
C (mm)
D (mm)
E (mm)
> 300
> 600
> 300
> 2000
> 600
5.3 Distance between the units
5.2 Minimum operational distances
OUTDOOR UNIT
A
Indoor Unit
B
B
Maximum difference in height
Outdoor Unit
Indoor Unit
Indoor Unit
Model
Difference
maximum
between
Internal Units
(A)
Difference
maximum
between
Internal Unit
and external unit
(B)
Distance
maxim
between
Internal Unit
and external unit
Length
maxim
total
of tubes
Length
total
Standard (m)
Additional gas charge
beyond the standard
total length (g / m)
m
m
m
m
m
g/m
XEVO-0917-M3E
-
10
25
25
5
12
XEVO-1217-M3E
-
10
25
25
5
12
XEVO-1817-D3E
10
15
25
40
15
15
XEVO-2717-T3E
10
15
30
60
22,5
15
5. UNITS POSITIONING