3. USE OF FAN
AUTO
It’s essential to include a motorized valve in the
water circuit in order to prevent the formation of
condensation.
The unit is a hydronic terminal and its operating
mode depends on the chiller or boiler.
Attention!
The signal is automatically sent to the fan; the display will briefly show the
symbol
.
AUTO
25
28
Tw
Fan stop
Fan start
Keep the state
Note:
Te
: Environment temperature
Ts
: Set temperature
Tw
: Water temperature
3.4 Operation in ventilation mode
1
Press the
MODE
key to select the
operating mode.
The fan recirculates the ambient air without heating or cooling it.
2
The temperature can be selected but is not effect
3
Pressing the
FAN
button, select the fan speed:
AUTO
Low
Medium
High
Auto*
4
Pressing the
button to select the desired position of the baffle
Attention!
The signal is automatically sent to the fan; the display will briefly show
the symbol
.
3.5 Operation in cooling mode “Cool”
Press the
MODE
key to select the
operating mode.
Use the
- +
keys to set the desired room temperature (16÷30 °C).
The temperature can be set degree by degree.
Use the
FAN
key to select the desired fan speed:
AUTO
Low
Medium
High
Auto*
Cooling operation system
- valve open
- fan running at set speed
(MAX if AUTO)
- valve open
- fan running at set speed (MAX if
AUTO)
- valve closed
- the fan remains stopped for 5 minu-
tes, and then restarts at MIN speed
for 1 minute.
- Internal temperature display to
display fixed Ts-1
- valve open
- fan running at set speed (MED if
AUTO)
- valve open
- fan running at set speed (MIN if
AUTO)
- After 1 minute valve closed and the
fan is stopped
- the fan remains stopped for 5 minu-
tes, and then restarts at MIN speed
for 1 minute.
Ts-1
Ts+2
Te
Ts
Ts+1