CONFIGURABLE INPUTS SELECTIONS
0 REMOTE START ON LOAD
2 AUXILIARY MAINS FAIL
3
4
5
6 SIMULATE AUTO BUTTON
7 SIMULATE TEST BUTTON
8
9 SIMULATE START BUTTON
10 SIMULATE STOP BUTTON
11 GENERATOR CLOSED AUXILIARY
In AUTO mode, if one of the configurable inputs are selected as 0 (Remote Start On Load), the unit doesn't
perform the mains failure control in order to start the generator. In AUTO mode, if one of the configurable inputs
are selected as 0 (Remote Start
) and this input is active, then the unit will perform the start sequence
and transfer load to the generator. If the input is passive, the unit will perform the stop sequence.
The unit will monitor the incoming single or three phase supply for Over Voltage, Under Voltage, Over Frequency
or Under Frequency. It may be required to monitor a different mains supply or some aspect of the incoming
mains not monitored by the unit. If the devices providing this additional monitoring are connected to operate this
input, the unit will operate as if the incoming mains supply has fallen outside of limits, the generator will be
instructed to start and take load. Removal of the input signal will cause the unit to act if the mains has returned to
within limits.
This input mimic's the operation of the 'Auto' button and is used to provide a remotely located Auto mode push
button.
This input mimic's the operation of the 'Test' button and is used to provide a remotely located Test mode push
button.
This input mimic's the operation of the 'Start' button and is used to provide a remotely located start push button.
This input mimic's the operation of the 'Stop' button and is used to provide a remotely located Stop push button.
This input is used to provide feedback to allow the unit to give true indication of the contactor or circuit breaker
switching status. It should be connected to the generator load switching device auxiliary contact.
On Load
If this input is active, operation will be similar to the ‘Remote Start On Load’ function except that the generator will
not be instructed to take the load. This function can be used where an engine only run is required e.g. for
exercise.
This input is used to prevent the unit from loading the generator. If the generator is already on load, activating
this input will cause the unit to unload the generator. Removing the input will allow the generator to be loaded
again.
This input only operates to control the generator-switching device if the unit load switching logic is
attempting load the generator. It will not control the generator-switching device when the mains is on load.
This input is used to provide feedback to allow the unit to give true indication of the contactor or circuit breaker
switching status. It should be connected to the generator load switching device auxiliary contact.
This input is used to prevent the unit from loading the mains supply. If the manis supply is already on load,
activating this input will cause the unit to unload the mains supply. Removing the input will allow the mains to be
loaded again.
This input only operates to control the mains-switching device if the unit load switching logic
is attempting to load the mains. It will not control the mains-switching device when the generator is on load.
1 REMOTE START OFF LOAD
12 GENERATOR LOAD INHIBIT
Note:
13 MAINS CLOSED AUXILIARY
14 MAINS LOAD INHIBIT
Note:
RESERVED
RESERVED
RESERVED
RESERVED