4.2.5 Outputs

Min

Default Unit

CONF. OUTPUT-1 (

)

Outputs->Conf. output-1

Max

0

1

0

131

0

43

Polarity

Function

0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)

0-NOT USED
1-AIR FLAP CONTROL
2-ALARM RESET
3-AUDIBLE ALARM
4-AUTO START INHIBIT
5-RESERVED
6-BATTERY HIGH VOLTAGE
7-BATTERY LOW VOLTAGE
8-CALLING FOR SCHEDULED RUN(EXERCISE)
9-CAN ECU POWER
10-CAN ECU STOP
11-CHARGE ALTERNATOR FAILURE
12-COMMON ALARM
13-COMMON ELECTRICAL TRIP ALARM
14-COMMON SHUTDOWN ALARM
15-COMMON WARNING ALARM
16-COOLING FAN AFTER START
17-COOLING FAN AFTER STOP
18-COOLANT TEMPERATURE HIGH PRE-ALARM
19-COOLANT TEMPERATURE HIGH SHUTDOWN
20-COOLING DOWN TIMER IN PROGRESS
21-CRANK RELAY ENERGISED
22-DELAYED ALARMS ACTIVE
23-DIGITAL INPUT1 ALARM
24-DIGITAL INPUT2 ALARM
25-DIGITAL INPUT3 ALARM
26-DIGITAL INPUT4 ALARM
27-DIGITAL INPUT5 ALARM
28-RESERVED
29-RESERVED
30-RESERVED
31-RESERVED
32-RESERVED
33-RESERVED
34-RESERVED
35-RESERVED
36-RESERVED
37-RESERVED
38-RESERVED
39-EMERGENCY STOP
40-FAIL TO START ALARM
41-FAIL TO STOP ALARM
42-CONF. AI1 CONTROL
43-FUEL RELAY ENERGISED
44-GAS ENGINE IGNITION OUTPUT
45-GENERATOR AT REST
46-GENERATOR AVAILABLE
47-GENERATOR CLOSED AUXILIARY
48-GENERATOR FAILED TO CLOSE
49-GENERATOR FAILED TO OPEN
50-GENERATOR HIGH FREQUENCY PRE-ALARM
51-GENERATOR HIGH FREQUENCY SHUTDOWN
52-GENERATOR HIGH VOLTAGE PRE-ALARM
53-GENERATOR HIGH VOLTAGE SHUTDOWN
54-GENERATOR LOAD INHIBIT
55-GENERATOR LOW FREQUENCY PRE-ALARM
56-GENERATOR LOW FREQUENCY SHUTDOWN
57-GENERATOR LOW VOLTAGE PRE-ALARM
58-GENERATOR LOW VOLTAGE SHUTDOWN
59-GENERATOR STOPPING
60-GENERATOR OPEN BREAKER
61-HORN OUTPUT LATCHED
62-HORN OUTPUT PULSED
63-LAMP TEST
64-RESERVED
65-LOSS OF MAGNETIC PICK-UP SPEED SIGNAL
66-LOW TEMPERATURE
67-MAINTENANCE DUE ALARM
68-RESERVED
69-RESERVED
70-RESERVED
71-RESERVED
72-RESERVED
73-RESERVED
74-RESERVED
75-RESERVED
76-RESERVED
77-RESERVED
78-NO LOADING COMMAND
79-OIL PRESSURE LOW PRE-ALARM
80-OIL PRESSURE LOW SHUTDOWN
81-CONF.AI1.HIGH PREA
82-CONF.AI1.HIGH SHUT
83-OVER CURRENT PRE-ALARM
84-OVER CURRENT
85-OVER POWER PRE-ALARM
86-OVER POWER SHUTDOWN
87-OVERSPEED PRE-ALARM
88-OVERSPEED SHUTDOWN
89-PANEL LOCK
90-PRE-HEAT(during preheat timer)
91-PRE-HEAT(until end of cranking)
92-PRE-HEAT(until end of warming)
93-PRE-HEAT(until end safety on)
94-REMOTE START PRESENT
95-REMOTE STOP DELAY IN PROGRESS
96-SHORT CIRCUIT
97-SMOKE LIMITING
98-STARTING ALARM
99-STARTING ALARMS ARMED
100-STOP RELAY ENERGISED
101-SYSTEM IN AUTO MODE
102-SYSTEM IN MANUAL MODE
103-SYSTEM IN STOP MODE
104-SYSTEM IN TEST MODE
105-UNDER CURRENT PRE-ALARM
106-UNDER CURRENT
107-UNDER POWER PRE-ALARM
108-UNDER POWER SHUTDOWN
109-UNDERSPEED PRE-ALARM
110-UNDERSPEED SHUTDOWN
111-WAITING FOR GENERATOR
112-RESERVED
113-LOAD SUPPLY FROM GENERATOR
114-RESERVED
115-CONFIGURABLE ANALOG INPUT 1 LOW PRE-ALARM
116 CONFIGURABLE ANALOG INPUT 1 LOW SHUTDOWN
117-RESERVED
118-RESERVED
119-RESERVED
120-RESERVED
121-CHOKE ACTIVE
122-REMOTE CONTROL ACTIVE
123-REVERSE POWER
124-RESERVED
125-RESERVED
126-RESERVED
127-RESERVED
128-HEATER CONTROL
129-REMOTE OUTPUT
130-UNBALANCE LOAD
131-WATER PUMP

(only available at Trans-MidiAUTO.CAN)

(only available at Trans-MidiAUTO.CAN)

(only available at Trans-MidiAUTO.MPU)

-

Содержание Trans-midiAUTO.CAN.232.GPRS

Страница 1: ...hanical reliability of the device Use a cloth dampened in ethyl alcohol or water to clean the external plastic case 1 Introduction 1 1 General Specifications The unit provides automatic start and stop...

Страница 2: ...ning installation of this product please read the instruction manual and warnings below carefully 2 Installation indekiler 2 1 Unit Configuration indekiler 2 2 Panel Mounting The unit is designed for...

Страница 3: ...l Sender or Configurable Analog Input Temperature Sender Oil Sender 36 35 18 19 BATTERY BATTERY 38 Sender Common 21 20 16 17 15 22 RX TX RS 232 J1939 ECUs 34 BATTERY 33 32 31 30 29 High Temperature or...

Страница 4: ...setting Technician setting Factory adjustment TECHNICIAN SETTING Password 0162 TECHNICIAN SETTING Password 0000 TECHNICIAN SETTING System Generator Engine Inputs TECHNICIAN SETTING System Generator E...

Страница 5: ...delay time Unit GENERATOR LEVEL FREQ Generator level Frequency 75 0 75 0 Hz 30 0 Nominal Alternator Frequency 50 0 43 0 Hz Nominal frequency Under freq shutdown Generator Under Frequency Shutdown 30...

Страница 6: ...to Scroll Number Scroll Time For Error Messages 0 0 dis 250 Sec 5 18 2 1 250 Auto scroll number 1 Err mesg scroll time Auto scroll time Sec 1 ENGLISH ENA DISBL BL DISBL Min Default Unit BREAKERS Syste...

Страница 7: ...ings Max Save setting to default Reset default sets Save setting to def Reset default sets YES NO NO Reset factory sets Reset factory sets YES NO NO YES NO NO Min Default Unit COMMUNICATION System Com...

Страница 8: ...t Max Generator Under Current Pre Alarm Reset Generator Under Current Actions Delay Time Generator Current Over IDMT Alarm Generator Over Current Set Generator Over Current Pre Alarm Generator Over Cu...

Страница 9: ...rse power set Reverse power act Rv pow act delay time GEN LEVEL POWER Generator Power level Generator Under Delay Time Power Action 0 dis 0 3 99 0 dis 2 Sec Generator Under Actions Disable Warning Ala...

Страница 10: ...dis Min Default Unit ENG CRANK DISCONNECT Engine Crank disconnect Max Crank Disconnect On Gen Frequency Crank Disconnect On Gen Voltage Crank Disconnect On Charge Alt Voltage 30 0 Crank Disconnect On...

Страница 11: ...alue 0 100 Speed set point 1500 1500 1800 Speed Set Point Selection RPM ENABL DISBL ENABL DISBL ENABL DISBL ENABL DISBL ENABL DISBL DISBL Baud Rate 0 20 1 50 2 100 3 125 4 250 5 500 6 800 7 1 000 J193...

Страница 12: ...enerator Followed By Shutdown After Cooling 4 Shutdown Alarm And Shutdown 2 0 2 0 0 dis 4 Amber warn activation Amber warn actions Sec J1939 Amber Warning Lamp Delay 2 0 250 Amber warn delay J1939 Amb...

Страница 13: ...day 1 Start time on monday 2 Start time on monday 3 Start time on monday 4 Stop time on monday 1 Stop time on monday 2 Stop time on monday 3 Stop time on monday 4 Start time on tues 1 Start time on tu...

Страница 14: ...on day 4 Satur Exercise Stop Time on day 1 Sun Exercise Stop Time on day 2 Sun Exercise Stop Time on day 3 Sun Exercise Stop Time on day 4 Sun Start time on day 1 fri Start time on day 2 fri Start tim...

Страница 15: ...pres sensor break Oil press input type 0 dis 60 0 dis 70 Low Temperature Warning C Low temp warning Conf AI1 unit Configurable Analog Input 1 Type Conf AI1 low shutdwn 0 dis 0 Not Used Disable 1 Digit...

Страница 16: ...e Analog Input 1 control OFF 3000 0 dis 0 dis 3000 Conf AI1 control ON Configurable Analog Input 1 control ON Conf AI1 high shutd Configurable Analog Input 1 High Shutdown 0 dis 3000 0 dis 90 0 3000 C...

Страница 17: ...Point 4 Configurable Analog Input 1 Point 5 15 31 49 66 85 101 117 132 149 178 579 404 342 250 179 136 103 77 67 63 10 30 50 70 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1300 1300 1300 130...

Страница 18: ...Point 6 Configurable Analog Input 1 Point 7 Configurable Analog Input 1 Point 8 Configurable Analog Input 1 Point 9 Configurable Analog Input 1 Point 10 110 130 150 170 190 0 0 0 0 0 1300 1300 1300 1...

Страница 19: ...2 Always Active Input active delay in 26 in2 24 in3 24 in4 26 in5 25 1 in 25 in2 0 in3 4 in4 25 in5 25 1 in1 2 2 in3 1 in4 5 2 in1 0 in2 0 in3 4 in4 0 in5 0 in1 2 2 in3 4 2 in5 2 in1 2 0 in3 5 in4 5 0...

Страница 20: ...LTAGE PRE ALARM 58 GENERATOR LOW VOLTAGE SHUTDOWN 59 GENERATOR STOPPING 60 GENERATOR OPEN BREAKER 61 HORN OUTPUT LATCHED 62 HORN OUTPUT PULSED 63 LAMP TEST 64 RESERVED 65 LOSS OF MAGNETIC PICK UP SPEE...

Страница 21: ...PUT 2 Outputs Conf output 2 CONF OUTPUT 3 Outputs Conf output 3 CONF OUTPUT 4 Outputs Conf output 4 CONF OUTPUT 5 Outputs Conf output 5 CONF OUTPUT 6 Outputs Conf output 6 Polarity Polarity Polarity P...

Страница 22: ...250 5 4 2 6 Timers Warmup Time 3 0 250 Warming up time Sec Note dis disable cont continuous Min Default STOPPING TIMERS Timers Stopping timers Max Remote Stop Delay Cooling Time 4 0 250 60 0 dis 3600...

Страница 23: ...rrent I offset 2 Current I offset 3 Current I1 Offset Current I Offset 2 Current I Offset 3 20 20 20 AV AV AV Min Default Unit BATTERY CHRG GEN VOL User adjustment Battery chrg gen vol Max 0 0 0 5 0 5...

Страница 24: ...Max operating current is 370 mA Battery voltage can be 0 VDC for max 50 ms during cranking battery voltage should be at least nominal voltage before cranking 8 to 32 V accuracy 1 FS resolution 0 1 V 3...

Страница 25: ...et controller speed sensing from Magnetic Pickup RS 232 communication Auto Start GenSet controller CanBus J1939 ECU communication RS 232 communication Auto Start GenSet controller speed sensing from M...

Отзывы: