EMKO TRANS-AMF Скачать руководство пользователя страница 24

24

4.2.6 Outputs

Min

Default Unit

CONF. OUTPUT-1 (

)

Outputs->Conf. output-1

Max

0

1

0

138

0

43

Polarity

Function

0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)

0-NOT USED
1-AIR FLAP CONTROL
2-ALARM RESET
3-AUDIBLE ALARM
4-AUTO START INHIBIT
5-AUXILIARY MAINS FAILURE
6-BATTERY HIGH VOLTAGE
7-BATTERY LOW VOLTAGE
8-CALLING FOR SCHEDULED RUN(EXERCISE)
9-CAN ECU POWER
10-CAN ECU STOP
11-CHARGE ALTERNATOR FAILURE
12-COMMON ALARM
13-COMMON ELECTRICAL TRIP ALARM
14-COMMON SHUTDOWN ALARM
15-COMMON WARNING ALARM
16-COOLING FAN AFTER START
17-COOLING FAN AFTER STOP
18-COOLANT TEMPERATURE HIGH PRE-ALARM
19-COOLANT TEMPERATURE HIGH SHUTDOWN
20-COOLING DOWN TIMER IN PROGRESS
21-CRANK RELAY ENERGISED
22-DELAYED ALARMS ACTIVE
23-DIGITAL INPUT1 ALARM
24-DIGITAL INPUT2 ALARM
25-DIGITAL INPUT3 ALARM
26-DIGITAL INPUT4 ALARM
27-DIGITAL INPUT5 ALARM
28-DIGITAL INPUT6 ALARM
29-DIGITAL INPUT7 ALARM
30-EXPANSION INPUT1 ALARM
31-EXPANSION INPUT2 ALARM
32-EXPANSION INPUT3 ALARM
33-EXPANSION INPUT4 ALARM
34-EXPANSION INPUT5 ALARM
35-EXPANSION INPUT6 ALARM
36-EXPANSION INPUT7 ALARM
37-EXPANSION INPUT8 ALARM
38-EARTH FAULT
39-EMERGENCY STOP
40-FAIL TO START ALARM
41-FAIL TO STOP ALARM
42-CONF. AI1 CONTROL
43-FUEL RELAY ENERGISED
44-GAS ENGINE IGNITION OUTPUT
45-GENERATOR AT REST
46-GENERATOR AVAILABLE
47-GENERATOR CLOSED AUXILIARY
48-GENERATOR FAILED TO CLOSE
49-GENERATOR FAILED TO OPEN
50-GENERATOR HIGH FREQUENCY PRE-ALARM
51-GENERATOR HIGH FREQUENCY SHUTDOWN
52-GENERATOR HIGH VOLTAGE PRE-ALARM
53-GENERATOR HIGH VOLTAGE SHUTDOWN
54-GENERATOR LOAD INHIBIT
55-GENERATOR LOW FREQUENCY PRE-ALARM
56-GENERATOR LOW FREQUENCY SHUTDOWN
57-GENERATOR LOW VOLTAGE PRE-ALARM
58-GENERATOR LOW VOLTAGE SHUTDOWN
59-GENERATOR STOPPING
60-GENERATOR OPEN BREAKER
61-HORN OUTPUT LATCHED
62-HORN OUTPUT PULSED
63-MASTER AUTO READY
64-CONF. AI2 CONTROL
65-LOSS OF MAGNETIC PICK-UP SPEED SIGNAL
66-LOW TEMPERATURE
67-MAINTENANCE DUE ALARM
68-MAINS CLOSED AUXILIARY
69-MAINS FAILED TO CLOSE
70-MAINS FAILED TO OPEN
71-MAINS FAILURE
72-MAINS HIGH FREQUENCY
73-MAINS HIGH VOLTAGE
74-MAINS LOAD INHIBIT
75-MAINS LOW FREQUENCY
76-MAINS LOW VOLTAGE
77-MAINS OPEN BREAKER
78-NO LOADING COMMAND
79-OIL PRESSURE LOW PRE-ALARM
80-OIL PRESSURE LOW SHUTDOWN
81-CONF.AI1.HIGH PREA
82-CONF.AI1.HIGH SHUT
83-OVER CURRENT PRE-ALARM
84-OVER CURRENT
85-OVER POWER PRE-ALARM
86-OVER POWER SHUTDOWN
87-OVERSPEED PRE-ALARM
88-OVERSPEED SHUTDOWN
89-PANEL LOCK
90-PRE-HEAT(during preheat timer)
91-PRE-HEAT(until end of cranking)
92-PRE-HEAT(until end of warming)
93-PRE-HEAT(until end safety on)
94-REMOTE START PRESENT
95-REMOTE STOP DELAY IN PROGRESS
96-SHORT CIRCUIT
97-SMOKE LIMITING
98-STARTING ALARM
99-STARTING ALARMS ARMED
100-STOP RELAY ENERGISED
101-SYSTEM IN AUTO MODE
102-SYSTEM IN MANUAL MODE
103-SYSTEM IN STOP MODE
104-SYSTEM IN TEST MODE
105-UNDER CURRENT PRE-ALARM
106-UNDER CURRENT
107-UNDER POWER PRE-ALARM
108-UNDER POWER SHUTDOWN
109-UNDERSPEED PRE-ALARM
110-UNDERSPEED SHUTDOWN
111-WAITING FOR GENERATOR
112-DUAL COMMUNICATION ERROR
113-LOAD SUPPLY FROM GENERATOR
114-LOAD SUPPLY FROM MAINS
115-CONFIGURABLE ANALOG INPUT 1 LOW PRE-ALARM
116 CONFIGURABLE ANALOG INPUT 1 LOW SHUTDOWN
117-CONFIGURABLE ANALOG INPUT 2 LOW PRE-ALARM
118-CONFIGURABLE ANALOG INPUT 2 LOW SHUTDOWN
119-CONFIGURABLE ANALOG INPUT 2 HIGH PRE-ALARM
120-CONFIGURABLE ANALOG INPUT 2 HIGH SHUTDOWN
121-CHOKE ACTIVE
122-REMOTE CONTROL ACTIVE
123-REVERSE POWER
124-CABIN TEMPERATURE LOW PRE-ALARM
125-CABIN TEMPERATURE LOW SHUTDOWN
126-CABIN TEMPERATURE HIGH PRE-ALARM
127-CABIN TEMPERATURE HIGH SHUTDOWN
128-HEATER CONTROL
129-REMOTE OUTPUT
130-UNBALANCE LOAD
131-WATER PUMP
132-RESERVED
133-RESERVED
134-RESERVED
135-RESERVED
136-SYNCHRON POSITION
137-OVER LOAD STEP 1
138-OVER LOAD STEP 2

-

Содержание TRANS-AMF

Страница 1: ...ins failure Intended for unattended operation it is able to detect failure of any phase of the mains and to start and switch over to a generator if the mains voltage goes outside pre set limits Both a...

Страница 2: ...nected to ground only one side Before commissioning the device parameters must be set in accordance with desired use Incomplete or incorrect configuration can cause dangerous stiuations Before beginni...

Страница 3: ...Input 2 Sender Common 18 19 17 H L J1939 ECUs 34 33 BATTERY 32 31 30 29 28 High Temperature or Configurable Input 5 Low Oil Pressure or Configurable Input 4 Water Level or Configurable Input 3 Configu...

Страница 4: ...PROGRAM Operator setting Technician setting Factory adjustment PROGRAM Operator setting Technician setting Factory adjustment TECHNICIAN SETTING Password 0162 TECHNICIAN SETTING Password 0000 TECHNIC...

Страница 5: ...tdown Delay Time GENERATOR VOLT LEVEL Generator level Volt 0 0 10 0 1 0 Sec 75 0 30 0 dis 75 0 75 0 Hz 30 0 dis Min Default Max Generator Under Frequency Pre Alarm Generator Under Frequency Pre Alarm...

Страница 6: ...RKING CALENDAR Generator Working calendar 23 59 23 59 23 59 23 59 23 59 23 59 23 59 23 59 23 59 23 59 23 59 23 59 23 59 23 59 H Min H Min H Min H Min H Min H Min H Min H Min H Min H Min H Min H Min H...

Страница 7: ...e Selection 7 Min Default Unit BREAKERS System Breakers Max Hardware Breaker Selection Gen Close Breaker Contact Type Gen Close Breaker Relay Type Gen Close Timer 0 Gen Open Breaker Relay Type 0 2 Gen...

Страница 8: ...Default Unit PASSWORD SETTINGS System Password settings Max Operator Password Technician Password 0 0 9999 0 9999 0 Operator password Technician password Min Default Unit DEFAULT SETTINGS System Defau...

Страница 9: ...r freq prealarm Over freq reset Shutdown delay time Unit GENERATOR LEVEL FREQ Generator level Frequency 75 0 75 0 Hz 30 0 Nominal Alternator Frequency 50 0 43 0 Hz Nominal frequency Under freq shutdow...

Страница 10: ...dis 2 AV AV AV 0 0 dis 0 0 dis 0 0 0 dis 9999 9999 9999 3 99 9999 9999 1 dis 5 dis 2 9999 9990 AV AV AV AV AV Sec Sec Sec Generator Under Current Actions Disable Warning Alarm Only No Shutdown Electr...

Страница 11: ...lay time Over load step 1 Over load step 1 rest Over load step 1 act Over load step 1 dly Reverse power set Reverse power act Rv pow act delay time GEN LEVEL POWER Generator Power level Generator Unde...

Страница 12: ...Sensing Opt Pickup En Dis Flywheel DISBL 1000 All Warnings Are Latched En Dis Changed To Stop Mode On Shutdown Fail Sens opt pickup flywh All warning are latch Stop mode on shutdown ENABL DISBL ENABL...

Страница 13: ...55 17 1 3 1 kBaud ECU remote control Speed control enable Oil pres cont enab Temp control enable ENABL Device Address 0 dis SPN version ECU Remote Control via J1939 Speed Control via J1939 Oil Pressur...

Страница 14: ...nly No Shutdown 3 Electrical Trip Alarm Off Load Generator Followed By Shutdown After Cooling 4 Shutdown Alarm And Shutdown 2 0 2 0 0 dis 4 Amber warn activation Amber warn actions Sec J1939 Amber War...

Страница 15: ...art time on monday 4 Stop time on monday 1 Stop time on monday 2 Stop time on monday 3 Stop time on monday 4 Start time on tues 1 Start time on tues 2 Start time on tues 3 Start time on tues 4 Stop ti...

Страница 16: ...on day 4 Satur Exercise Stop Time on day 1 Sun Exercise Stop Time on day 2 Sun Exercise Stop Time on day 3 Sun Exercise Stop Time on day 4 Sun Start time on day 1 fri Start time on day 2 fri Start tim...

Страница 17: ...ure shutdown Oil pressure reset Oil pressure prealarm Oil press input type 0 dis 70 Low Temperature Warning C Low temp warning Conf AI1 unit Configurable Analog Input 1 Type 0 dis 0 Not Used Disable 1...

Страница 18: ...ime Fuel Filling Maximum Time 30000 Fuel fill alarm reset Fuel consumpt reset Fuel tank capacity Fuel Filling Alarm Reset Fuel Consumption Reset Fuel Tank Capacity NO NO 100 YES NO YES NO 250 0 Sec 0...

Страница 19: ...Point 4 Configurable Analog Input 1 Point 5 15 31 49 66 85 101 117 132 149 178 579 404 342 250 179 136 103 77 67 63 10 30 50 70 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1300 1300 1300 130...

Страница 20: ...ender Point 6 Configurable Analog Input 2 Sender Point 7 Configurable Analog Input 2 Sender Point 8 Configurable Analog Input 2 Sender Point 9 Configurable Analog Input 2 Sender Point 10 Configurable...

Страница 21: ...In6 26 1 in 25 in2 3 in3 4 in4 25 in5 25 in6 7 1 in1 2 in2 3 1 in4 5 2 in6 1 in1 0 in2 0 in3 4 in4 0 in5 0 in6 0 in1 2 2 in3 4 2 in5 6 2 in1 0 in2 3 5 in4 5 0 in6 5 in1 3 1 in2 4 0 in5 6 0 If Select F...

Страница 22: ...on 6 Simulate Auto Button 7 Simulate Test Button 8 Simulate Manual Button 9 Simulate Start Button 10 Simulate Stop Button 11 Generator Closed Auxiliary 12 Generator Load Inhibit 13 Mains Closed Auxili...

Страница 23: ...st Button 8 Simulate Manual Button 9 Simulate Start Button 10 Simulate Stop Button 11 Generator Closed Auxiliary 12 Generator Load Inhibit 13 Mains Closed Auxiliary 14 Mains Load Inhibit 15 Auto Resto...

Страница 24: ...LATCHED 62 HORN OUTPUT PULSED 63 MASTER AUTO READY 64 CONF AI2 CONTROL 65 LOSS OF MAGNETIC PICK UP SPEED SIGNAL 66 LOW TEMPERATURE 67 MAINTENANCE DUE ALARM 68 MAINS CLOSED AUXILIARY 69 MAINS FAILED TO...

Страница 25: ...Conf output 6 CONF EXP OUTPUT 1 Outputs Conf exp output 1 CONF EXP OUTPUT 2 Outputs Conf exp output 2 CONF EXP OUTPUT 3 Outputs Conf exp output 3 CONF EXP OUTPUT 4 Outputs Conf exp output 4 CONF EXP...

Страница 26: ...ec Mains Return Delay 5 0 3600 Mains return delay Sec 4 2 8 Expansion Modules IO 1 8 MODULE Expansion modules IO 1 8 Expansion I O Module Selection Disable enable select Min Default Max DISBL ENABL DI...

Страница 27: ...me Remote Priority Selection Disable enable select Node ID Working period Early start time Remote priority selct Min Default Max 1 0 00 0 0 dis 2 98 59 250 2 1 1 00 15 dis H Min Sec 0 Disable 1 Priori...

Страница 28: ...pment II Normal office or workplace non conductive pollution Continuous 8 to 32 V Peak 36 V Max operating current is 360mA Battery voltage can be 0 VDC for max 50 ms during cranking battery voltage sh...

Страница 29: ...Karanfil Sk No 6 16369 BURSA TURKEY Phone 90 224 261 1900 Fax 90 224 261 1912 Relay Outputs Transistor Outputs Approvals Generator contactor relay output 8A 250V Mains contactor relay output 8A 250V C...

Отзывы: