4.2.5 Inputs
Note :
These sensor types can only be used in the Trans-AMF.RS485 units.
The USB communication interface can not be used when one of these sensor types is
selected.
*1
Min
Default
Unit
SENDER INPUTS (
)
Inputs->Sender inputs
Max
Oil Pressure Input Type
Oil Pressure Pre-Alarm
Oil Pressure Pre-Alarm Reset
Coolant Temperature Input Type
1.2
0.0 (dis)
30.0
BAR
1.4
0.0
30.0
BAR
1.0
0.0
30.0
BAR
0 - Not Used (Disable)
1 - Digital NC
2 - Digital NO
3 - VDO 5 BAR
4 - VDO 7 BAR
5 - VDO 10 BAR
6 - DATCON 5 BAR
7 - DATCON 7 BAR
8 - MURPHY 7 BAR
9 - User Configured
90
0 (dis)
300
88
0
300
95
0
300
Temperature Sensor Break
High Temperature Pre-Alarm
Oil Pressure Shutdown
High Temp. Pre-Alarm Reset
High Temperature Shutdown
C
C
C
Temp. sensor break
High temp. prealarm
High temp. reset
High temp. shutdown
Conf. AI1 type
Temp. input type
Oil pressure shutdown
Oil pressure reset
Oil pressure prealarm
Oil press. input type
0 (dis)
70
Low Temperature Warning
C
Low temp. warning
Conf. AI1 unit
Configurable Analog Input-1 Type
0 (dis)
0 - Not Used (Disable)
1 - Digital NC
2 - Digital NO
3 -
4 -
5
5 - DATCON
6 - MURPHY
7 - PT100
8 - User Configured
VDO 120 ºC
VDO 1 0 ºC
0 (dis)
0- Not Used (Disable)
1- Digital NC
2- Digital NO
3- VDO OHM (10-180)
4- VDO TUBE (90-0)
5- US OHM (240-33)
6- ELS11 OHM (0-190)
7- FORD (73-10)
8- ELS13 OHM (0-190)
9- ELS30 OHM (0-190)
10- DAVITEQ (RS485)
11- KUS CLS2 (RS485)
12- MSLL 790 (RS485)
13- CSFL 790 (RS485)
14- User Configured
*1
*1
*1
*1
0 (dis)
0 (dis)
Oil Pressure Unit
Oil pressure unit
BAR
BAR/PSI/KPA
Coolant Temperature Unit
Temperature unit
ºC
ºC/ºF
BAR/PSI/KPA/ºC/ºF/%/Lt
%
Configurable Analog Input-1 Unit
0 (dis)
0 (dis)
300
Coolant Heater Control On
C
Heater control ON
0
300
Coolant Heater Control Off
C
Heater control OFF
45
5
0
9999
Water Pump On Time
Water pump on time
0
9999
Water Pump Off Time
Sec
Water pump off time
5
Sec
0 - Disable
1 - Enable From Safety
On (3min. delayed)
2 - Always Enable
0 (dis)