ENGLISH
Digital Input Contact Selection Parameter
( Default = 1 ) MODBUS ADDRESS:40036
Digital input is inactive.
NO “normally open” digital input is active when the contact is closed.
NC “normally close” digital input is active when the contact is opened.
Digital Input Function Selection Parameter
If digital input contact selection parameter
( Default = 0 ) MODBUS ADDRESS:40037
value = 0, this parameter is not observed.
When the digital input is active, fan is stopped. screen will be displayed.
When the digital input is active, compressor is stopped. screen will be
displayed and defrost operation will be disabled. If Buzzer function selection
parameter = 2 or 4 buzzer is active.
When the digital input is active, first fan stops, 10 seconds later compressor
stops. will be displayed at main operation screen.
When the digital input is active, defrost starts.
When the digital input is active, alarm will be active. will be displayed at
main operation screen. If Buzzer function selection parameter = 2 or 4
buzzer is active.
12
Buzzer Function Selection Parameter
( Default = 0 ) MODBUS ADDRESS:40039
Buzzer is inactive.
Buzzer is active during defrost operation.
Buzzer is active if an alarm occurs.
Buzzer is active during cabinet sensor failures.
Buzzer is active during defrost, alarm or cabinet sensor failures.
Button Protection Parameter
( Default = 0 ) MODBUS ADDRESS:40041
There is no protection.
Defrost time set value can not be changed and manual defrost is not available.
Temperature set value can not be changed.
Defrost time set value and temperature set value can not be changed and
manual defrost is not available.
Buzzer Active Time
If buzzer function selection parameter
Buzzer active time can be define with this parameter. It can be adjusted from 1 to 99
minutes. When this parameter is 1, if decrement button is pressed, is observed. In
this condition buzzer is active till buzzer silence button is pressed.
( Default = ) MODBUS ADDRESS:40040
value = 0, this parameter is not observed.
Programming Mode Accessing Password
It is used for accessing to programming mode. It can be adjusted from 0 to 999. If it is 0,
password is not entered for accessing to the parameters. If password is ‘12’ only ,
, can be accesible.
( Default = 0 ) MODBUS ADDRESS:40044
Digital Input Effect Time Parameter
If digital input contact selection parameter
( Default = ) MODBUS ADDRESS:40038
value = 0, this parameter is not observed.
For digital input function selection parameter = 0 or 2, maximum effect time of digital
input is determined with this parameter. It can be adjust from 0 to 120 minutes. When this
parameter is 0, if decrement button is pressed, is observed. In this condition the
effect will be ended when digital input is deactive.
Defrost time can not be changed,Defrost ON/OFF operation is available.
PROKEY communication selected.
Communication Mode Selection Parameter
( Default = 0 )
MODBUS ADRESS:40042
RS485 communication selected.
Slave ID Parameter
( Default = 1 ) MODBUS ADDRESS=40043
Device communication address parameter (1 to 247)