  6.6.2. Page-2 Parameters

TECH. PW  

Password for entering to the technician section is defined with this parameter. 
If it is 0, technician section accessed without entering password.

OPR. PW 

Password for entering to the operator section is defined with this parameter. 
If it is 0, operator section accessed without entering password.

DSP. TYPE

Main operation screen type is adjusted by this parameter. If parameter value,
       1  = M
       2  = S

ultiple channel view

ingle channel view is selected.

DSP. SCAN 

If parameter value,

       0  = 
       1  = 

Display channel scanner mode is adjusted by this parameter. 

Display channel scanner mode OFF
Display channel scanner mode ON

SCAN TIME 

Display scan period is adjusted by this parameter. All main operation screen is displayed during time 
defined by this parameter. 

LANGUAGE 

Device Language is selected by this parameter. If parameter value,
       0  = TÜRKÇE 
       1  = ENGLISH

TECH. PW.

Technician Section Password

42106

-

9000

0

0

OPR. PW.

Operation Section Password

42107

-

9000

0

0

DSP. TYPE

Main Operation Screen Type

42128

2

1

2

-

DSP. SCAN

Display Scan ON/OFF

42129

1

0

1

ON/OFF

SCAN TIME

Display Scan Period

42130

3600

1

2

SEC.

LANGUAGE

Device Language Selection

42136

1

0

1

-

Parameter

Explanation

Unit

Min

Max

Default Address

If no operation is performed for 20 seconds in technician parameters section, device turns to 
main operation screen automatically.

i

Содержание EPLC9600-CHANNEL8

Страница 1: ...Relay or pnp source transistor output Sensor error detection Adjustable temperature offset 3 Different alarm and pre alarm types for each channel High Low and Band Alarms User defined channel labels D...

Страница 2: ...ined Operation Also in these sections there are warnings to prevent serious injury while doing the physical and electrical mounting or using the device Explanation of the symbols which are used in the...

Страница 3: ...TOR OUTPUTS 4 CABLE CONNECTION BETWEEN RS232 TERMINAL OF THE DEVICE AND PC 5 CONNECTION FOR RS485 SERIAL COMMUNICATION 6 DEFINETION OF THE FRONT PANEL AND ACCESSING TO THE PARAMETERS 6 1 DEFINETION OF...

Страница 4: ...EC The Low Voltage Directive 2004 108 EC The Electromagnetic Compatibility Directive has been designed and manufactured to the following specifications EN 61000 6 4 2007 EMC Generic Emission Standard...

Страница 5: ...ive Machine production industries etc Applications Heating Baking Ovens Incubators Storages Air Conditioning etc 1 Preface 1 1 General Specifications RS232 Communication Standard RS485 Modbus RTU Prot...

Страница 6: ...pairs should only be performed by trained and specialized personnel Cut power to the device before accessing internal parts Do not clean the case with hydrocarbon based solvents Petrol Trichlorethylen...

Страница 7: ...eep the power off until all of the wiring is completed so that electric shock and trouble with the unit can be prevented Never attempt to disassemble modify or repair this unit Tampering with the unit...

Страница 8: ...urface maximum thickness 15 mm 0 59 inch Mounting Clamp 2 1 General Description 2 2 EPLC9600 CHANNEL8 Front View and Dimensions of 96 mm 3 78 inch 96 mm 3 78 inch 12 1 mm 0 47 inch 84 mm 3 31 inch Max...

Страница 9: ...2 3 Panel Cut out 9 129 mm 5 08 inch min 92mm 3 62 inch 92mm 3 62 inch 129 mm 5 08 inch min...

Страница 10: ...2 4 Environmental Ratings Operating Temperature 0 to 50 C Max Operating Humidity 90 Rh non condensing Altitude Up to 2000m Operating Conditions Forbidden Conditions Corrosive atmosphere Explosive atm...

Страница 11: ...vice will not fall while doing the montage 2 6 Installation Fixing Clamp The unit is designed for panel mounting 1 Insert the unit in the panel cut out from the front side 2 Insert the mounting clamps...

Страница 12: ...t the unit against damage and to prevent failure Keep the power off until all of the wiring is completed so that electric shock and trouble with the unit can be prevented 3 Electrical Wirings 3 1 Term...

Страница 13: ...T CH 2 ALARM OUTPUT CH 3 ALARM OUTPUT CH 4 ALARM OUTPUT CH 5 ALARM OUTPUT CH 6 ALARM OUTPUT CH 7 ALARM OUTPUT CH 8 ALARM OUTPUT GENERAL ALR OUTPUT GENERAL PRE ALR OUTPUT 5 x 5A 250VV USB 2 0 COMMUNICA...

Страница 14: ...3 ALARM OUTPUT CH 4 ALARM OUTPUT CH 5 ALARM OUTPUT CH 6 ALARM OUTPUT CH 7 ALARM OUTPUT CH 8 ALARM OUTPUT GENERAL ALR OUTPUT GENERAL PRE ALR OUTPUT USB 2 0 COMMUNICATION ETHERNET OR RS485 COMMUNICATION...

Страница 15: ...ower supply switch and a fuse must be added to the supply voltage input Power supply switch and fuse must be put to a place where user can reach easily Power supply switch must be two poled for sepera...

Страница 16: ...supply voltage There is no power supply switch on the device So a power supply switch must be added to the supply voltage input In accordance with the safety regulations the power supply switch shall...

Страница 17: ...V Relay Outputs RS 232 RS 485 Usb 2000V V Ethernet 3 5 Galvanic Isolation Test Values of EPLC9600 CHANNEL8 with Relay Outputs Analog inputs 17 Supply Input of Device 14 15 2000V V 2000V V 2000V V 200...

Страница 18: ...RS 232 RS 485 Usb 2000V V 1500V V Ethernet 3 6 Galvanic Isolation Test Values of EPLC9600 CHANNEL8 with Transistor Outputs Analog inputs 500V V 500V V Supply Input of Output Card 2000V V 500V V 500V...

Страница 19: ...er 9 Pin DCON connection Cable Lenght must be max 12 meters for 9600 baud rate 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 TX NA RX GND NA NA 19 4 Cable Connection...

Страница 20: ...d Cable lenght can be maximum 1000 meters in 9600 baud rate When baud rate increases cable lenght must be decreased 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 D D...

Страница 21: ...tering the symbol character for string type variables in variable value changing screen DOWN BUTTON This button is used to decrement the digit which cursor is show of variable in variable value changi...

Страница 22: ...right button for accessing the main operation screen 2 If the display scan parameter value DSP SCAN 1 each main operation screen is showing on LCD screen during time defined by SCANTIME parameter val...

Страница 23: ...y SCANTIME parameter value i If more than one alarm messages is present each alarm message is showing on LCD screen during 1 second i 23 MAIN OPERATION CHANNEL 4 SCREEN MAIN OPERATION CHANNEL 1 SCREEN...

Страница 24: ...button for accessing to password entering screen Enter the operator parameter section password with cursor lef right up and down buttons OPERATOR PARAMETER SCREEN CHANNEL 1 PARAMETERS Press enter butt...

Страница 25: ...ameter screen Other operator section parameters can be accessed with same method explained above press escape button for return to main operation screen 25 Minimum Maximum 200 0 650 0 100 0 Change the...

Страница 26: ...chnician parameter section password with cursor lef right up and down buttons TECHNICIAN PARAMETER SCREEN PAGE 1 CHANNEL 1 PARAMETERS Press enter button for accessing to the technician section paramet...

Страница 27: ...ng next parameter page press up button for accessing previous parameter page TECHNICIAN PARAMETER SCREEN PAGE 6 RS 485 PAGE TECHNICIAN PARAMETER SCREEN PAGE 7 USB PAGE Press down button for accessing...

Страница 28: ...o main operation screen Press down button for accessing next parameter page press up button for accessing previous parameter page If the device has a optional ETHERNET communication then ETHERNET page...

Страница 29: ...left side of the display and can be selected by pressing the channel selection buttons i Min Max Default Unit ALARM SET Alarm Set Value For Channel X O C 650 0 200 0 100 0 PRE A SET Pre Alarm Set Valu...

Страница 30: ...m disable 1 Sensor break alarm enable 6 6 1 Page 1 Parameters Technician Parameter Page Number Min Max Default Unit ALARM TYPE Alarm Type For Channel X 3 1 2 PRE A TYPE Pre Alarm Type For Channel X 3...

Страница 31: ...2053 CH 2 BAND ALARM 42057 CH 3 BAND ALARM 42061 CH 4 BAND ALARM 42065 CH 5 BAND ALARM 42069 CH 6 BAND ALARM 42073 CH 7 BAND ALARM 42177 CH 8 BAND ALARM 42181 Parameter Name CH 1 SENSOR ALARM Modbus A...

Страница 32: ...play channel scanner mode OFF Display channel scanner mode ON SCAN TIME Display scan period is adjusted by this parameter All main operation screen is displayed during time defined by this parameter L...

Страница 33: ...1 1 0 1 ENA DIS CH 5 I O Channel 5 Enable Disable 42112 1 0 1 ENA DIS CH 6 I O Channel 6 Enable Disable 42113 1 0 1 ENA DIS CH 7 I O Channel 7 Enable Disable 42114 1 0 1 ENA DIS CH 8 I O Channel 8 Ena...

Страница 34: ...r RS232 is can be adjusted by this parameter If parameter value ID Modbus communication device ID for RS232 is can be adjusted by this parameter This parameter value is can be adjusted from 1 to 247 e...

Страница 35: ...sted by this parameter If parameter value ID Modbus communication device ID for RS485 is can be adjusted by this parameter If the device has a optional RS485 communication then RS 485 page is observed...

Страница 36: ...130 6 129 1 130 5 129 5 130 0 129 9 130 3 129 1 SAMPLE 2011 06 23 17 26 09 130 6 129 1 130 5 129 5 130 0 129 9 130 3 129 1 SAMPLE 2011 06 23 17 26 10 130 6 129 1 130 5 129 5 130 0 129 9 130 3 129 1 SA...

Страница 37: ...be adjusted by this parameter If DHCP is selected as a enable there is no need to adjust to this parameter if DHCP is selected as a disable then user must adjust this parameter 37 PORT SET Ethernet p...

Страница 38: ...meter 38 SECOND Second value for RTC time is adjusted by this parameter Press and hold on 3 seconds Enter button for setting the RTC time value Min Max Default Unit YEAR Year Value For RTC Time 3000 2...

Страница 39: ...ue Alarm Output SET HYS SET HYS ON OFF Alarm Output Process Value BandAlarm SET SET BAND 2 SET BAND 2 HYS HYS SET Alarm or Pre Alarm Set value HYS Hysteresis value forAlarm and Pre Alarm output BAND B...

Страница 40: ...alue Address 30001 O C CH 2 P VALUE Channel 2 Process Value 30002 O C CH 3 P VALUE Channel 3 Process Value 30003 O C CH 4 P VALUE Channel 4 Process Value 30004 O C CH 5 P VALUE Channel 5 Process Value...

Страница 41: ...Break Protection Upscale Sampling Time 400msecs Input Ressistance 10MW Digital Output Transistor or relay outputs Transistor Output PNP source type transistor output M Relay Output Resistive Load 5A 2...

Отзывы: