49
Defines type and scale of sensor for RTD input. It is active if RTD input
is selected.
PT-100 ( -200°C ; 650°C ) or ( -328°F ; 1202°F)
PT-100 ( -199.9°C ; 650.0°C ) or ( -199.9°F ;999.9°F)
No point
Fixed dual point calibration is done. It does not allow to
adjust minimum and maximum value of calibration points. It
can be adjusted from -1999 to 9999
It allows to define 16 calibration points.
It allows to do selectable dual point calibration.
Defines input range and scale of
Z
Voltage / Current input.It is
active if
Z
Voltage / Current is selected.
0...50mV
Z
( -1999 ; 9999 )
0...5V
Z
( -1999 ; 9999 )
0...10V
Z
( -1999 ; 9999 )
0...20mA
Z
( -1999 ; 9999 )
4...20mA
Z
( -1999 ; 9999 )
Defines point position for displays. It is active if
oltage / Current
input is selected.
Z
V
It is active when
oltage / Current input is selected. It determines
calibration type.
Z
V
It defines minimum value for selectable dual point calibration. It is
active if
oltage / Current input is selected. It can be adjusted from
-1999 to 9999.
Z
V
It defines maximum value for selectable dual point calibration. It is
active if
oltage / Current is selected. It can be adjusted from -1999
to 9999.
Z
V
In multi point calibration, calibration points are defined with these
parameters.
It is active if
oltage / Current is selected. It can be adjusted from
-1999 to 9999.
In multi point calibration operation, defined scale is divided into 16
calibration points.
For example :
is (0-50 mV
) .
Z
V
Z
Between second and third digits “0.00”
Between third and fourth digits. “0.000”
Between first and second digits “0.0”