ACC: Access Password

▶ 

[123]

 Complete parameter menu

▶ 

[231]

 Allows changing the measurement unit from °C to °F

▶ 

[99]

 Reset factory parameters

▶ 

[55]

 Field test

P02: Control differential normal setpoint (hysteresis):

It is the temperature difference between ON and OFF of the compressor output in NORMAL and 

SUPER FREEZING MODES.

P03: Ambient temperature S1 indication (offset):

This parameter makes it possible to correct the temperature displayed by the S1 sensor.

P04 and P05: Minimum/Maximum setpoint allowed to the user:

These are the minimum and maximum temperatures set with password so that the user does not 

exceed these limits when changing the temperature without an access password

P06: Instrument powering-on delay

It delays the process start to avoid several devices turning on at the same time. 

Note: 

During the delay, only the temperature will be shown in the display while all outputs will be 

off.

P07: High ambient temperature alarm (S1)

Monitors Sensor 1 and displays the message (AH) when the temperature is above the value 

configured in this parameter. It emits an audible alarm, if P41 is enabled. This parameter will be 
disabled in the following situations:

▶ From the time the controller was powered up until the SetPoint is reached the first time.
▶ During defrost cycles

The differential for shutdown is fixed at 0.1°C in relation to the alarm temperature.

P08: Refrigeration time (defrost interval)

It is the running time of the compressor for refrigeration mode.

12

USER

 MANUAL

TEMPERATURE CONTROLLER

STORM 

ST

201

7. DESCRIPTION OF THE PARAMETERS

Содержание STORM ST201

Страница 1: ...01 ENGLISH REV 02 USE FOR COLD STORAGE ROOMS AND VISA COOLERS ELECTRICAL AND HOT GAS DEFROSTING FRONT PANEL IP65 ECO AND SUPER FREEZING MODE PROGRAMABLE BY NFC APP EVEN UNPLUGGED BUZZER SHORTCUT KEYS...

Страница 2: ...3 Easy Menu Features 3 1 SUF Activate Super Freezing Mode 3 2 Eco Select Eco Mode 3 3 Dfr Manual defrost 3 4 Loc Lock Functions 3 5 Ctl Control Functions Off 3 6 SP Edit Normal Setpoint 3 7 SPE Edit E...

Страница 3: ...al design that harmonizes with various types and colors of equipment Front Panel IP65 Ambient temperature sensor for ON OFF Compressor Defrost sensor for monitoring the evaporator temperature Temperat...

Страница 4: ...te electromagnetic interference such as motors meters relays and solenoids IMAGE 1 Easy Key Upper Key Lower Key Enter Key Fan Control Locked Functions Off Temperature Unit Indication Degrees Celsius C...

Страница 5: ...via the application or directly through the front keys of the controller The number of different con gurations with the Emicol Easy App is unlimited depending only on the memory capacity of the cell p...

Страница 6: ...plete parameter menu 231 Change the unit of measure to Celsius or Fahrenheit The parameters are retained this change will not reset to the factory settings Shortcut tip Press the keys simultaneously t...

Страница 7: ...sed time to enter economic mode If P42 configured as Digital input P29 Maximum time in economic mode 3 2 ECO ACTIVATE ECO MODE Press and then to dFr Press and ON and the symbol will appear Shortcut ti...

Страница 8: ...SP Press With the keys edit the desired temperature value in the Normal SETPOINT Press to save 3 6 SP EDIT NORMAL SETPOINT Press and then to SPE Press With the keys edit the desired temperature value...

Страница 9: ...er P43 Instantaneous temperature at sensor S3 If enabled in parameter P42 3 10 INFORMATION ABOUT THE PROCESS IN PROGRESS CRTL Press until appears CRTL turns controller functions on off LOC pressed tog...

Страница 10: ...9 Evaporator temperature S2 for fan return after draining 105 50 C 30 P22 Fan stop for high temperature in evaporator 30 0 NO min 1 P20 Maximum time for fan return after drainage fan delay 15 0 NO min...

Страница 11: ...at any time to exit the mode and restart the controller Simultaneously press the to return to the selection menu between controlling the outputs or display inputs 11 USER MANUAL TEMPERATURE CONTROLLER...

Страница 12: ...sword P06 Instrument powering on delay It delays the process start to avoid several devices turning on at the same time Note During the delay only the temperature will be shown in the display while al...

Страница 13: ...ps the compressor on Option 2 Cycles according to the times of P32 and P33 P12 Defrost at start of instrument This parameter allows you to set an additional defrost when starting the controller useful...

Страница 14: ...In this period all the outputs remain off To disable adjust time 0 no P19 Evaporator temperature S2 for fan return after draining It is the maximum temperature at Sensor 2 to turn the fan on again af...

Страница 15: ...ol to turn the compressor on and off P27 Control differential economic ECO hysteresis It is the temperature difference between ON and OFF the compressor output in ECONOMIC mode MODE P28 Time for close...

Страница 16: ...shut down control outputs Turns off all outputs if the S3 sensor reaches a higher temperature de ned in the parameter This parameter is voided until the Setpoint is reached the rst time The warning Ah...

Страница 17: ...N Setpoint ECO N O 3 Digital IN Defrost N O 4 Digital IN Super Freezing N O 5 Digital IN External alarm N O 6 Digital IN Door contact N O 7 Digital IN Setpoint ECO N C 8 Digital IN defrost N C 9 Digit...

Страница 18: ...tion The ST201 2HP controller will be able to work with different types of temperature sensors avoiding the need for exchanging in cases of dif culty when cabling Example cold rooms SF9 Standard SCL O...

Страница 19: ...In Economic mode Fan delay process Locked Functions Activates function lock Sensor1 error Disconnected damaged or short circuited Sensor2 error disconnected damaged or short circuited Sensor3 error D...

Страница 20: ...an generate dangerous or harmful situations for people Emicol guarantees the product and is exempted from any and all extra expenses such as inputs services or transportation 10 WARRANTY AND REPAIRS D...

Отзывы: