The VPAC/VPHP 30-36 offers an economic benefit
when used in a multi-room suite by supplying condi-
tioned air to more than one room without the need to
install another PTAC/PTHP. This is also a design ad-
vantage since the second room does not need an ex-
terior wall for a second unit.

The VPHP 30-36 heat pump is intended to be a lim-
ited range heat pump, which means utilizing a supple-
mented heat option is recommended since heat pump
operation will cease at approximately 40°F outdoor
temperature. Consult factory for availability of a full
range defrosting heat pump version.

Each system is supplied with a ready-to-install wall
sleeve and outdoor louver. The cabinet is constructed
with 20 gauge galvanized steel with a G-90U corro-
sion resistant rating and the insulated top discharge
evaporator compartment provides quiet ducted, con-
ditioned air delivery to other room location(s).

The VPAC/VPHP 30-36 is backed by EMI and ECR
International and is tested and rated in accordance
with ARI standard 390 and UL-1995. Due to ongoing
product development, product designs and specifica-
tions may change without notice. Please contact the
factory for more information

.

CONDENSATE REMOVAL

The VPAC/VPHP 30-36 requires an internal drain sys-
tem due to its unique draw-thru condenser design.
Condenser side drain stub(s) are integral to the chas-
sis and are very easy to connect a drain hose to.

AIR SYSTEMS

Motors are thermally protected PSC type. Air stream
surfaces are insulated with 1/4 inch fiberglass or 1/8
inch volara. The evaporator fan is a forward curved
type directly mounted to the motor shaft. The con-
denser propeller utilizes a draw-thru design for im-
proved efficiency.

PRODUCT DESCRIPTION

The VPAC/VPHP 30-36 single package vertical air
conditioner (SPVAC) and heat pump (SPVHP) cre-
ates new options in layout and space utilization. The
VPAC/VPHP 30-36 offers low cost operation and quiet,
comfortable air distribution, especially when used in
multi-room suites, apartments, healthcare facilities,
and homes.

Framed into a concealed closet enclosure for low op-
erating sound levels, the VPAC/VPHP 30-36’s verti-
cal discharge vent allows ducting to the top of the
room(s) for superior air circulation and distribution. Mul-
tiple air supply grilles can distribute air when used with
a soffit and intake grilles can be located on the sides
of the enclosure.

The VPAC/VPHP 30-36 can be applied in a ducted
return air application or can remain non-ducted as de-
livered. If ducted, the closet enclosure does not re-
quire minimum clearances other than what is recom-
mended for adequate service access. If non-ducted,
minimum clearance options must be adhered to as
dictated for optimal performance and sound. See note
on minimum clearance dimensions in the illustation
titled ”Exploded View Of Typical Installation” on page
2 of this document.

 (Figure 1)

VPAC/VPHP 30-36

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

Nominal Cooling Capacity: 30,000 - 36,000 Btuh

P/N 240-4554 Rev. 1.0 [03/04]

VPAC/VPHP 30-36 Single Package Vertical Air Conditioner

(SPVAC) and Heat Pump (SPVHP)

Содержание VPAC30

Страница 1: ...S Motors are thermally protected PSC type Air stream surfaces are insulated with 1 4 inch fiberglass or 1 8 inch volara The evaporator fan is a forward curved type directly mounted to the motor shaft...

Страница 2: ...uld result in serious injury or electrical shock All field wiring must be done in accordance to NEC and local codes Check the unit rating plate for circuit ampacity and breaker s or fuse size s Use on...

Страница 3: ...nd sound levels that a minimum clearance of 6 between the enclosure and the chassis be main tained It is also very important that the rough opening in the wall for the wall sleeve and louver be the co...

Страница 4: ...ressure e s p Speed tap changes may need to be made from factory settings and Envi FIGURE 5 RETURN AIR ACCESS PANEL NOTE Available with solid doors if separate intake is used Access Panel Frame Frame...

Страница 5: ...an limit the heat ing or cooling range of the thermostat A non mer cury electronic thermostat is available if needed Please contact the factory for more information SELECTING A COMPATIBLE THERMOSTAT W...

Страница 6: ...fan will continue to run to aid in the defrost process ELECTRIC HEAT OPERATION Place the thermostat system switch in heat mode Ad just the set point temperature above the room tem perature The electri...

Страница 7: ...connections Terminal ends that are loose will eventually fail causing a loss of performance or worse 5 Check fan motors and blower assemblies Some units may require a drop of light oil to motors and...

Страница 8: ...Max HACR Number Amps HP RLA LRA Amps HP Amps Voltage Breaker 30 208 230 60 1 1 7 0 25 14 73 3 0 5 18 7 197 22 3 35 36 208 230 60 1 1 7 0 25 16 3 88 3 0 5 21 197 25 1 40 VOLTS HZ PH M C A Condenser Fa...