Made in rome, new York, usa
s2Ha High Capacity Condensing unit
s2H dIMEnsIons and sPECIFICatIons
notE:
All EMI products are subject to ongoing development programs so design and
specifications may change without notice.
s2H ELECtrICaL sPECIFICatIons
ModEL
(1)
VoLts/HZ/PHasE
Fan
CoMPrEssor 1 CoMPrEssor 2 totaL
aMPs
MIn. CIr.
aMPs
(2)
HaCr
BrKr
rLa
HP
rLa
Lra
rLa
Lra
9900
208-230/60/1
1.8
0.33
3.4
23
3.4
23
8.6
9.5
15
2200
208-230/60/1
1.8
0.33
4.3
27
4.3
27
10.4
11.5
15
9200
208-230/60/1
1.8
0.33
3.4
23
4.3
27
9.5
10.6
15
(1) Circuit Designators: 9 = 9,000 Btuh • 2 = 12,000 Btuh (ex. - Model 9200 consists of one 9,000 Btuh compressor and one 12,000 Btuh compressor)
(2) Always refer to the rating plate for Minimum Circuit Ampacity on all multiple compressor units.
1/2” Diameter Lag Holes
4.63”
4.63”
28.74”
12.44”
3.00”
s2H PIPInG sPECIFICatIons
sound data
sHIPPInG
WEIGHt
Model#
Line sizes
Liquid
suction
dBa
Lbs.
9900
1/4”
1/2”
64
159
2200
1/4”
1/2”
65
197
9200
1/4”
1/2”
65
187
44”
38”
15”
Electrical
connections
Front of unit
Easy access interconnects
on back of unit