ELECTRICAL WORK

Minimum norminal cross-sectional 
area of conductors: 

Rated current 
of appliance
         (A)

>3  and  <6

>6  and  <10

>10  and  <16
>16  and  <25

Nominal cross-sectional 
                 area

2

                (mm )

0.75

1

1.5

2.5

NOTE

: The cable size and the current of the fuse 

or switch are determined by the maximum current
indicated on the nameplate which located on the 
side panel of the unit. Please refer to the nameplate 
before selecting the cable, fuse and switch.
  

Connect the cable to the outdoor unit

Connect the cable to the indoor unit

NOTE: Before performing any electrical 
work, turn off the main power to the system.

,

1. The inside and outside connecting cable can 
    be connected without removing the front grille.
2. The indoor power cord type is H05VV-F or
    H05V2V2-F, the outdoor power cord and 
    interconnected cord type is H07RN-F.
3. Lift the indoor unit panel up, remove the 
    electrical box cover by loosening the screw
    as shown in Fig.22.
4. Ensure the colour of wires of outdoor unit 
    and the terminal Nos. are the same to the 
    indoor s respectively.
5. Wrap those cables not connected with 
    terminals with insulation tapes, so that they 
    will not touch any electrical components. 
    Secure the cable onto the control board with 
    the cord clamp.

,

Terminal block of indoor unit

Fig.22

To outdoor unit

To outdoor unit

1. Remove the cover control from the unit by 

loosening the 3 screws. See Fig.23.

2. Dismount caps on the conduit panel.
3. Temporarily mount the conduit tubes(not included) 
    on the conduit panel.
4. Properly connect both the power supply and low 
    voltage lines to the corresponding terminals on
    the terminal block.
5. Ground the unit in accordance with local codes.
6. Be sure to size each wire allowing several inches 
    longer than the required length for  wiring.
7. Use lock nuts to secure the conduit tubes.  

G

G

Cover control

Over 

1 3/5i

n.(40m

m)

Terminal block

Conduit panel

Connecting 
cable

Power supply 
cord

Outdoor unit

Fig.23a

L    N    S

L1  L2    S

or

Electrical box
cover

Front Panel

Содержание enviroair szi ZHA

Страница 1: ...Inverter Split Systems Installation Operation Manintenance Manual Air Handler Indoor Models ZWHA ZWHB Condenser Outdoor Models ZHA ZHB An ISO 9001 2008 Certified Company ECR International Inc 2201 Dwy...

Страница 2: ...0 TEST RUNNING Test running 15 AIR PURGING Air purging with vacuum pump 13 Safety and leakage check 13 SOCIABLE REMARK SAFETY PRECAUTIONS OPERATING INSTRUCTIONS CARE AND MAINTENANCE OPERATION TIPS TRO...

Страница 3: ...hysical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safe...

Страница 4: ...ring standard regulation and this installation instructions An independent circuit and single outlet must be used If electrical circuit capacity is not enough or defect found in electrical work it wil...

Страница 5: ...by arrows from wall or other obstacles Do not place animals and plants in the path of the air inlet or outlet Take the air conditioner weight into account and select a place where noise vibration and...

Страница 6: ...m abo ve 30cm above Air Filter Air Filter Air Outlet 30cm above Wrapping tape B 200cm above Additional drain pipe Accessories Parts you must purchase Consult the dealer about the pipe size 6 35 9 53 1...

Страница 7: ...mensions are in mm unless otherwise stated 1 Determine hole positions according to the diagramdetailed in Fig 5 Drill one 1 hole 65mm slanting slightly to outdoor side 2 Always use wall hole conduit w...

Страница 8: ...the indoor unit with a cushioning material between the indoor unit and the wall Get it out after finish piping 4 Push the lower part of the indoor unit up on the wall then move the indoor unit from s...

Страница 9: ...hose sloped downward to drain out the condensed water smoothly CAUTION Install the outdoor unit on a rigid base to prevent increasing noise level and vibration Determine the air outlet direction where...

Страница 10: ...r tube pipe in a downward direction as you remove burrs in order to avoid dropping burrs into the tubing Pipe Reamer Point down Fig 16 Fig 17 Outdoor unit dimension mm WxHxD A mm B mm 530 290 484 600...

Страница 11: ...air conditioner and explain to the client until the problem is solved 2 Power voltage should be in the range of 90 110 of rated voltage 3 The creepage protector and main power switch with a 1 5 times...

Страница 12: ...osening the screw as shown in Fig 22 4 Ensure the colour of wires of outdoor unit and the terminal Nos are the same to the indoor s respectively 5 Wrap those cables not connected with terminals with i...

Страница 13: ...onnecting means must be provided and shall be located within sight from and readily accessible from the air conditioner Connecting cable with conduit shall go through the hole of the conduit panel Not...

Страница 14: ...in the fixed wiring and have an air gap contact separation of at least 3mm in each active phase conductors CAUTION CAUTION CAUTION CAUTION Air and moisture in the refrigerant system have undesirable...

Страница 15: ...ully open the handle Lo of the manifold valve 4 Operate the vacuum pump to evacuate After starting evacuation slightly loose theflare nut of the Lo valve on the gas pipe side and check that the air is...

Страница 16: ...ing If bubbles come out the pipes have leakage 2 Leak detector Use the leak detector to check for leakage Test running Safety and leakage check TEST RUNNING Manual control button AUTO COOL Perform tes...

Страница 17: ...er please read this manual carefully and keep it for future reference INVERTER SPLIT TYPE ROOM AIR CONDITIONER 16 Before using your air conditioner please read this manual carefully and keep it for fu...

Страница 18: ...ABLE REMARK DISPOSAL Do not dispose this product as unsorted municipal waste Collection of such waste separately for special treatment is necessary It is prohibited to dispose of this appliance in dom...

Страница 19: ...y cause fire and electric shock It may cause explosion fire and burns It may cause electric shock or fire due to heat generation It may cause electric shock It may cause failure of machine or electric...

Страница 20: ...cond itioner to preserve preci sion devices food pets plants and art objects It may cause deterioration of quality etc It may cause failure of product or fire Do not use for special purposes Turn off...

Страница 21: ...Horizontal air flow grille 6 Vertical air flow louver inside 7 Display panel 8 Connecting pipe drain hose 9 Connective cable 10 Connecting pipe 11 Stop valve Indoor unit Outdoor unit 8 NOTE The indoor...

Страница 22: ...DIGITAL DISPLAY Displays the current setting temperature and malfunction protection code when the air conditioner is in operation Displays the room temperature under fan only mode 1 2 3 4 Ion Indicato...

Страница 23: ...HIGH fan mode 3 Optimum performance will be achieved within these operating temperature Suggestion For the unit adopts an Electric Heater when the outside ambient temperature O O is below 0 C 32 F we...

Страница 24: ...the vertical louver can be adjusted by using the remote controller Please refer to the REMOTE CONTROLLER OPERATION MANUAL for details Do not operate the air conditioner for long periods with the air...

Страница 25: ...will switch off This characteristic maintains both enery saving and comfort in night operation DRYING operation The fan speed will be automatically controlled under dry operation During the dry opera...

Страница 26: ...maintenance Turn the system off before cleaning To clean wipe with a soft dry cloth Do not use bleach or abrasives NOTE Supply power must be disconnectd before cleaning the indoor unit Filter Handle C...

Страница 27: ...e to water can destroy the insulation leading to possible electric shock When cleaning the unit first make sure that the power and circuit breaker are turned off Caution Air freshening filter Air fres...

Страница 28: ...relative humidity A white mist may generate due to moisture generated from defrosting process when the air conditioner restarts in HEAT mode operation after defrosting 3 Low noise of the air conditio...

Страница 29: ...controller will stop the unit completely When the power restores or pressing the ON OFF button on the remote controller again the unit restarts automatically with all the previous settings including t...

Страница 30: ...Windows are open Air inlet or outlet of indoor or outdoor unit has been blocked Compressor 3 minutes protection has been activated If the trouble has not been corrected please contact a local dealer o...

Отзывы: